Meaning of the LED displays
The following tables contain the meaning of the status and error displays.
RN/ER/MT LEDs on the interface module
Table 5- 1
Status and error displays of RN/ER/MT LEDs
LEDs
RN
ER
(RUN)
(ERROR)
Off
Off
On
On
Not relevant Not rele-
Flashes
Not relevant Not rele-
On
Not rele-
vant
Flashes
Not rele-
Not relevant
vant
Flashes
Flashes
* PWR LED on (on the interface module): Check the backplane bus for a short-circuit.
IM 155-6 PN HF interface module (6ES7155-6AU00-0CN0)
Manual, 03/2015, A5E03915895-AF
MT
(MAINT)
Missing or insufficient supply voltage on
interface module.
Off
Test of LEDs during startup: The three
LEDs light up simultaneously for ap-
On
proximately 0.25 s.
Interface module is deactivated.
vant
Interface module is not configured.
ET 200SP starts up.
ET 200SP is being assigned parame-
ters.
ET 200SP is currently exchanging data
vant
with the IO controller.
Not rele-
Group errors and group error channels.
vant
The configured structure does not cor-
respond to the actual structure of
theET 200SP .
Invalid configuration states.
Parameter assignment error in the I/O
module.
Maintenance.
On
The "Node flash test" is run (LEDs LK1
and LK2 of the PROFINET interface
Flashes
also flash).
Hardware or firmware defective (LEDs
LK1 and LK2 of the PROFINET inter-
face do not flash).
Interrupts, error messages, diagnostics and system alarms
Meaning
5.1 Status and error displays
Remedy
Check the supply voltage or turn it on at the
interface module.*
---
Activate the interface module with the con-
figuration software or the user program.
Configure the interface module with the
configuration software.
---
---
Evaluate the diagnostics and eliminate the
error.
Check the structure of the ET 200SP to see
whether a module is missing or defective,
or whether a non-configured module is
inserted.
See section Invalid configuration states of
the ET 200SP on PROFINET IO (Page 45).
Evaluate the display of the module status in
STEP 7 and eliminate the error in the re-
spective I/O module.
See section Maintenance events
(Page 41).
---
Run a firmware update. If the error persists,
contact Siemens Industry Online Support.
Replace the interface module.
35