Connection Instructions; Terminal Block - Mitsubishi Electric MELSERVO-J4 MR-J4 A Series Instruction Manual

General-purpose ac servo
Table of Contents

Advertisement

11. OPTIONS AND AUXILIARY EQUIPMENT
Note 1.
For power supply specifications, refer to section 1.3.
2.
For the servo amplifier of 7 kW, always disconnect the lead wire of built-in regenerative resistor, which is connected to the P+
and C terminals.
3.
Always connect between P3 and P4 terminals. (factory-wired) Use either the power factor improving DC reactor or the power
factor improving AC reactor. When using the power factor improving DC reactor, refer to section 11.11.
4.
Connect P/+ and N/- terminals of the brake unit to a correct destination. Incorrect connection destination results in servo
amplifier and brake unit malfunction.
5.
Contact rating: 1b contact, 110 V AC_5 A/220 V AC_3 A
Normal condition: TH1-TH2 is conducting. Abnormal condition: TH1-TH2 is not conducting.
6.
Contact rating: 230 V AC_0.3 A/30 V DC_0.3 A
Normal condition: B-C is conducting/A-C is not conducting. Abnormal condition: B-C is not conducting/A-C is conducting.
7.
Do not connect more than one cable to each P+ to N- terminals of the servo amplifier.
8.
Always connect BUE and SD terminals. (factory-wired)
9.
Connect MSG and SD terminals of the brake unit to a correct destination. Incorrect connection destination results in servo
amplifier and brake unit malfunction.
10.
For the cable to connect the terminal block and the P+ and N- terminals of the servo amplifier, use the cable indicated in (3)(b)
of this section.
11.
Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop
deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn
off the magnetic contactor.
12.
Configure up a circuit to turn off EM2 when the main circuit power is turned off to prevent an unexpected restart of the servo
amplifier.
13.
When wires used for L11 and L21 are thinner than wires used for L1, L2, and L3, use a molded case circuit breaker.

(2) Connection instructions

The cables between the servo amplifier and the brake unit, and between the resistor unit and the brake
unit should be as short as possible. Always twist the cable longer than 5 m (twist five times or more per
one meter). Even when the cable is twisted, the cable should be less than 10 m. Using cables longer
than 5 m without twisting or twisted cables longer than 10 m, may result in the brake unit malfunction.
Servo amplifier
(3) Cables
(a) Cables for the brake unit
For the brake unit, HIV cable (600 V grade heat-resistant PVC insulated wire) is recommended.
1) Main circuit terminal
N/-
P/+

Terminal block

Brake unit
P+
P/+
P
N-
N/-
PR
5 m or less
5 m or less
Brake unit
PR
200 V
FR-BU2-15K
class
FR-BU2-30K
Servo amplifier
Resistor unit
P
PR
Crimp
Main
terminal
circuit
terminal
N/- P/+
screw
PR
size
M4
5.5-4
M5
5.5-5
11 - 18
Brake unit
Twist
Twist
P+
P/+
P
N-
N/-
PR
10 m or less
10 m or less
Wire size
Tightenin
g torque
N/- P/+ PR
[N•m]
HIV wire
2
[mm
]
1.5
3.5
2.5
5.5
Resistor unit
P
PR
AWG
12
10