ABB i-bus KNX Product Manual page 122

Switch/shutter actuator
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus® KNX PARAMETERS
7.6.1.8
DEPENDENT PARAMETER
Lower threshold
This parameter is used to define the lower threshold. Default values and units depend on the option se-
lected in the Data type of group object "Threshold input" parameter.
Options
0 ... 20 ... 100 %
0 ... 100 ... 255
0 ... 10000 ... 65535
0 ... 18 ... 250 °C
0 ... 100 ... 100,000 lux
Condition for visibility:
Parameter window Logic/Threshold 1 \ Parameter Function of the logic gate \ Option Threshold
7.6.1.9
DEPENDENT PARAMETER
Change thresholds via KNX
This parameter defines whether the thresholds set in ETS can be changed via the ABB i-bus® KNX.
Options
No
Yes
Condition for visibility:
Parameter window Logic/Threshold 1 \ Parameter Function of the logic gate \ Option Threshold
7.6.1.10
DEPENDENT PARAMETER
Result if upper threshold is exceeded
This parameter can be used to define the result of the function Threshold when the value received at the
threshold input exceeds the upper threshold. The result can be linked with any output within the device
or output on the group object Result .
Options
Unchanged
1
0
Condition for visibility:
Parameter window Logic/Threshold 1 \ Parameter Function of the logic gate \ Option Threshold
Upper and lower thresholds can be set only in ETS.
The upper and lower thresholds can be changed via the ABB i-bus® KNX.
The following group objects are enabled depending on the settings in the parameter Data type of
group object "Threshold input":
Change upper threshold (DPT 5.001)
Change upper threshold (DPT 5.010)
Change upper threshold (DPT 7.001)
Change upper threshold (DPT 9.001)
Change upper threshold (DPT 9.004)
Change lower threshold (DPT 5.001)
Change lower threshold (DPT 5.010)
Change lower threshold (DPT 7.001)
Change lower threshold (DPT 9.001)
Change lower threshold (DPT 9.004)
The result of the function Threshold remains unchanged.
The result of the function Threshold is 1.
The result of the function Threshold is 0.
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 122