ABB i-bus KNX Product Manual page 112

Switch/shutter actuator
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus® KNX PARAMETERS
7.4.1.1
DEPENDENT PARAMETER
Automatically reset from manual operation to KNX operation
This parameter can be used to define whether the device is automatically reset from the operating state
Manual operation to the operating state KNX operation after an adjustable time.
Options
No
Yes
Condition for visibility:
Parameter window Manual operation \ Parameter Enable manual operation \ Option Yes
7.4.1.1.1
DEPENDENT PARAMETER
Automatic reset after
This parameter can be used to set the time after which the device is automatically reset to the operating
state KNX operation .
After the Manual operation button is pressed, the device remains in Manual operation mode until the
button is pressed again or the parameterized time elapses.
Options
00:00:30 ... 00:05:00 ... 18:12:15 hh:mm:ss
Condition for visibility:
Parameter window Manual operation \ Parameter Enable manual operation \ Option Yes  \ Parameter
Automatically reset from manual operation to KNX operation \ Option Yes
7.4.1.2
DEPENDENT PARAMETER
State after end of manual operation
This parameter can be used to define the state of the output after the end of manual operation.
Options
Manually set state retained
Refreshed KNX state
Condition for visibility:
Parameter window Manual operation \ Parameter Enable manual operation \ Option Yes
Automatic reset is disabled. The operating state can be changed only by using the Manual operation
button.
The device is automatically reset to the operating state KNX operation after the set time.
Automatic reset after
The manually set state remains active.
Manually set states are overwritten. The refreshed KNX state is used. More information → Refreshed
KNX state, Page 83.
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 112