Installation accessories
Fig. 19 Cleaning and fitting contact arms (120)
Fig. 20 Fitting contact arms (120)
16
1.
Firmly screw threaded rods onto contact faces.
Tightening torque for
M12: 40 ±4 Nm
M16: 100 ±10 Nm
Tightening torques apply to greased threads
only.
2.
Roughen the faces of the copper contact arms,
–
clean them and
–
grease them with with Atlantic Vaseline
(contact grease SN10611).
Clean faces with silver-plated contact faces
–
and grease them with with Atlantic Vase-
line (contact grease SN10611).
Fit the contact arms.
9229 0002 401 0A