Siemens SION 3AE Series Operating Instructions Manual page 14

Withdrawable module with vacuum circuit breaker and installation accessories
Hide thumbs Also See for SION 3AE Series:
Table of Contents

Advertisement

Installation
Fig. 13 Securing the busbars onto the busbar terminals
(143)
Fig. 14 Grounding the withdrawable frame (100)
12
Apply Atlantic Vaseline (contact grease SN10611)
to the bolts that will be utilized to bolt the busbars
onto the busbar terminals (143).
Firmly bolt the busbars onto the busbar terminals
(143).
Tightening torque for M12: 40 ±4 Nm
Tightening torque applies to greased threads only.
Fit the bushing covers (142) onto the bushing (140)
so that they engage in the recesses (A).
Ground the withdrawable frame (100) on the pres-
sure pads for the withdrawable section:
Screw suitable grounding cables or busbars
2
(2 x 100 mm
) with an M10 grounding screw onto
the through-holes (1) with the grounding symbol
labels ( ).
9229 0002 401 0A
2016-03-03

Advertisement

Table of Contents
loading

Table of Contents