Fig. 11 Securing the withdrawable frame (100) in the
functional unit
Fig. 12 Preparing the busbar terminals (143)
9229 0002 401 0A
2016-03-03
Secure the withdrawable frame (100) in the functional
unit, for example with blind rivets to ISO 15979-6.4 x
12-St/St
Busbars before assembly:
·
Use a steel brush to clean the busbar contact
surface.
·
Grease with Atlantic Vaseline (contact grease
SN10611) to protect against corrosion
Clean and grease silver-plated busbar terminals
(143)
Installation
11