Transport, Unpacking, Installation
2.3

Mounting

The following are required for mounting:
♦ M8 bolt(s)
♦ Dimension drawings: Fig. 2.2 for types of construction E, F, Fig. 2.3 for types of construction G and Fig. 2.4
Safe converter operation requires that the equipment is mounted and commissioned by
qualified personnel taking into account the warning information provided in this Instruction
Manual.
The general and domestic installation and safety regulations for work on electrical power
equipment (e.g. VDE) must be observed as well as the professional handling of tools and
the use of personnal protective equipment.
Death, severe bodily injury or significant material damage could result if these instructions
are not followed.
Chassis units do not provide any protection against direct contact. It is the users
responsibility to ensure and provide the correct protection against contact according to the
relevant accident prevention regulations VBG4, by appropriately designing the enclosure or
enclosures around the chassis unit.
Remove shipping brace (marked).
Requirements at the point of installation:
The local guidelines and regulations must be observed when mounting and installing the
equipment.
The unit is mounted corresponding to the dimension drawings in Section 2.4.
Equipment rooms must be dry and dust-free. Ambient and cooling air must not contain
any electrically conductive gases, vapors and dusts which could diminish the
functionality. Dust-laden air must be filtered.
When mounting in cabinets, a clearance of above and below must be provided so that the
cooling air flow is not restricted (refer to dimension drawings, Section 2.4).
Dimension the cabinet cooling in line with the power loss! (+ Section „Technical data")
The converter ambient climate in operating rooms may not exceed the values of code F according to DIN 40040.
For temperatures > 40 °C (104 °F) and installation altitudes > 1000 m, de-rating is required (+ Section
„Technical data").
2-2
for type of construction H.
WARNING
WARNING
SIMOVERT MASTER DRIVES
08.96
SIMOVERT
MASTER
DRIVES
Cooling air
≤ 40 °C (50 °C)
Fig. 2.1
Mounting the
converters in
cabinets
Siemens AG
6SE7087-6AH70
Operating Instructions