Siemens SIMOVERT FC Operating Instructions Manual page 53

Master drives, chassis units (types e - h)
Table of Contents

Advertisement

08.96
FC
VC
SC
Rated voltage, rated frequency, rated current
Rated voltage in V n
Input
Output
Rated frequency f n
Input
Output:
Rated current I n
Input
Output
DC link voltage V dn
Rated output
Auxiliary power supply
Loading Class II acc. to EN 60146-1-1
Rated current
Base load time
Overcurrent
Overcurrent time
Loading Class II acc. to EN 60146-1-1 (additionally for VC and SC)
Rated current
Base load time
Overcurrent
Overcurrent time
Losses, cooling, power factor
Power factor
Supply cosϕ 1N
Converter cosϕ U
Efficiency η
Pulse frequency 3 kHz
Power loss
Pulse frequency 3 kHz
Required cooling air flow
Pressure drop ∆p
Sound pressure level, dimensions, weights
Sound pressure level
Type
Width
Height
Depth
Weight
IP00
IP20
Siemens AG
6SE7087-6AH70
SIMOVERT MASTER DRIVES
Drive converter types
6SE70...
33-2EG10
6SE70...
33-2EG20
6SE70...
33-2EG30
V
3 AC 380 ... 460 ± 15 %
3 AC 0 ... Rated input voltage
Hz
FC
U/f = konst
U = konst
VC
U/f = konst
U = konst
SC
A
315
315
V
kVA
207...251
V
DC 24 (20-30) (3 A without Options; with Options refer to Section 6.1)
A
287
s
A
430
s
A
287
s
A
504
s
> 0,98
< 0,92 ind.
0,98
kW
5,19
m 3 /s
0,41
Pa
145
dB(A)
84
G
mm
508
1450
460
kg
165
196
Operating Instructions
33-7EH20
33-7EH20
50/60 ± 6 %
0 ... 300
8 ... 300
0 ... 600
8 ... 300
0 ... 400
370
370
510...620
244...295
337
240
503
60
337
270
592
30
> 0,98
< 0,92 ind.
0,98
6,83
0,57
256
86
H
508
1580
460
220
240
Technical Data
9-3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simovert vcSimovert sc

Table of Contents