Replacing the capacitor bank
The board consists of the DC link capacitors, the capacitor mounting element and the DC link connection.
♦ Types of construction E to F
• Release the electrical connection to the inverter
busbars
• Release the mechanical locking
• Swing-out the capacitor bank towards the front
and remove from the top.
• Install a new capacitor bank in the inverse sequence.
5.2.5
Replacing boards
Boards contain components which could be damaged by electrostatic discharge. The
human body must be discharged immediately before an electronics board is touched.
This can be simply done by touching a conductive, grounded object immediately beforehand
(e.g. bare metal cubicle components).
5.2.5.1
Replacing the PCU
♦ Types of construction E to F
• Remove connector X39.
• Remove the M6 bolts at the busbar connection
U1/L1;V1/L2;W1/L3; C; D and PE1
• Release the distance piece and remove the PCU
• Install the new PCU in the invserse sequence.
Siemens AG
6SE7087-6AH70
SIMOVERT MASTER DRIVES
The boards may only be replaced by qualified personnel.
It is not permissible that the boards are withdrawn or inserted under voltage.
Death, severe bodily injury or significant materal damage might result if these
instructions are not observed.
Operating Instructions
♦ Types of construction G to H
• Remove the connection for the symmetrical
resistor (cable lug M6)
• Release the mechanical mounting
• Swing-out the capacitor bank to the front and lift
out of the converter at a 45 ° angle.
WARNING
CAUTION
♦ Types of construction G to H
• Remove the PCC
• Remove connector X39.
• Remove bolts M6 at the bus connection
U1/L1;V1/L2;W1/L3; C; D and PE1
• Release the distance piece and remove the
PCU