Emerson Rosemount 3051N Reference Manual page 33

Smart pressure transmitter for nuclear service
Hide thumbs Also See for Rosemount 3051N:
Table of Contents

Advertisement

Reference Manual
00809-0100-4808, Rev CA
June 2008
HT
= URV + S (URV) P
c
Where:
HT
URV =
S =
P
s
In this example:
URV =
LRV =
P
s
S =
To calculate the corrected low trim (LT
LT
LT
To calculate the corrected high trim (HT
HT
HT
To complete a Rosemount 3051N full trim, enter the corrected values for low
trim (LT) and high trim (HT). Refer to "Full Trim" on page 2-18.
Enter the corrected input values for low trim and high trim through the
communicator keypad after you apply the nominal value of pressure as the
transmitter input.
NOTE
After calibrating Rosemount 3051N Range 4 and Range 5 transmitters for
high differential pressure applications, rerange the 4 and 20 mA points using
the communicator to maintain the systematic static line pressure correction.
You may re-zero the 4 mA point at line pressure after installation using the
local zero button without affecting the completed calibration.
Rosemount 3051N
s
=
Corrected High Trim Value
c
Upper Range Value
–(Span shift per specification)
=
Static Line Pressure
1500 inH
O
2
500 inH
O
2
=
1200 psi
-(-0.01/1000 psi) = 0.01/1000psi
) value:
c
=
500 in H
0 + (0.01/1000 psi)(500 in H
c
2
=
506 in H
O
c
2
) value:
c
=
1500 in H
0 + (0.01/1000 psi)(1500 in H
c
2
=
1518 in H
O
c
2
0)(1200 psi)
2
0)(1200 psi)
2
2-21