Emerson Rosemount 3051S Series Quick Start Manual
Emerson Rosemount 3051S Series Quick Start Manual

Emerson Rosemount 3051S Series Quick Start Manual

Pressure transmitter/flowmeter with foundation fieldbus protocol
Hide thumbs Also See for Rosemount 3051S Series:

Advertisement

Quick Start Guide
00825-0100-4805, Rev FB
June 2016
Rosemount
3051S Series Pressure Transmitter
and Rosemount 3051SF Series Flowmeter
with F
fieldbus Protocol
OUNDATION

Advertisement

Table of Contents
loading

Summary of Contents for Emerson Rosemount 3051S Series

  • Page 1 Quick Start Guide 00825-0100-4805, Rev FB June 2016 ™ Rosemount 3051S Series Pressure Transmitter and Rosemount 3051SF Series Flowmeter ™ with F fieldbus Protocol OUNDATION...
  • Page 2: Table Of Contents

    June 2016 Quick Start Guide NOTICE This guide provides basic guidelines for Rosemount 3051S Series Pressure Transmitters. It also provides the basic electronics guidelines for the Rosemount 3051SFA Reference Manual and Rosemount 3051SFC Reference Manual. It does not provide instructions for diagnostics, maintenance, service, or troubleshooting.
  • Page 3: Mount The Transmitter

    Quick Start Guide June 2016 1.0 Mount the transmitter 1.1 Liquid flow applications 1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Mount the transmitter so the Flow drain/vent valves are oriented upward. 1.2 Gas flow applications 1.
  • Page 4 June 2016 Quick Start Guide Figure 1. Panel and Pipe Mounting Panel mount Pipe mount Coplanar flange Traditional flange In-line Housings ™ PlantWeb Junction box Remote mount display...
  • Page 5 Use only bolts supplied ™ with the transmitter or sold by Emerson Process Management as spare parts. Figure 2 illustrates common transmitter assemblies with the bolt length required for proper transmitter assembly.
  • Page 6 June 2016 Quick Start Guide Table 1. Torque Values for the Flange and Flange Adaptor Bolts Bolt material Head markings Initial torque Final torque Carbon Steel (CS) 300 in-lb 650 in-lb Stainless Steel (SST) 150 in-lb 300 in-lb 1.5 O-rings with flange adapters Failure to install proper flange adaptor O-rings may cause process leaks, which can result in death or serious injury.
  • Page 7: Tagging

    Quick Start Guide June 2016 1.6 In-line gage transmitter orientation The low side pressure port (atmospheric reference) on the in-line gage transmitter is located under the sensor module neck label. (See Figure Keep the vent path free of any obstruction, including but not limited to paint, dust, and lubrication by mounting the transmitter so any contaminants can drain away.
  • Page 8: Consider Housing Rotation

    June 2016 Quick Start Guide Note The device description loaded in the host system must be at the same revision as this device. The device description can be downloaded from EmersonProcess.com/Rosemount or Fieldbus.org. 3.0 Consider housing rotation To improve field access to wiring or to better view the optional LCD display: 1.
  • Page 9 Quick Start Guide June 2016 4.4 Signal termination Every fieldbus segment requires terminators at each end of the segment. Failure to properly terminate segments may cause communication errors with devices on the segment. 4.5 Transient protection Transient protection devices require the transmitter be grounded for proper operation.
  • Page 10: Verify Configuration

    June 2016 Quick Start Guide 5.0 Verify configuration Use the following block examples to do basic configuration to the transmitter. For more advanced configurations see the Rosemount 3051S F fieldbus OUNDATION Reference Manual. Note ™ DeltaV users should use DeltaV Explorer for the resource and transducer blocks and Control Studio for the function blocks.
  • Page 11 Quick Start Guide June 2016 DP Flow example Parameters Enter data Channel L_Type Square root XD_Scale 0–100 inH O @ 68 °F Out_Scale 0–20 GPM DP Level example Parameters Enter data Channel L_Type Indirect XD_Scale 0–300 inH O @ 68 °F Out_Scale 0–25 ft To display pressure on the LCD meter...
  • Page 12: Trim The Transmitter

    June 2016 Quick Start Guide 6.0 Trim the transmitter Note Transmitters are shipped fully calibrated per request or by the factory default of full scale (span = upper range limit). 6.1 Zero trim A zero trim is a single-point adjustment used for compensating mounting position and line pressure effects.
  • Page 13: Product Certifications

    Quick Start Guide June 2016 7.0 Product Certifications 7.1 European Directive Information A copy of the EC Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EC Declaration of Conformity can be found at EmersonProcess.com/Rosemount.
  • Page 14: June

    June 2016 Quick Start Guide IE FM FISCO Certificate: 3012350 Standards: FM Class 3600 – 2011, FM Class 3610 – 2010, FM Class 3611 – 2004, FM Class 3810 – 2005, NEMA 250 – 2003 Markings: IS CL I, DIV 1, GP A, B, C, D; T4(-50 °C ≤ T ≤...
  • Page 15 Quick Start Guide June 2016 7.6 Europe E1 ATEX Flameproof Certificate: KEMA 00ATEX2143X Standards: EN 60079-0:2012, EN 60079-1: 2007, EN 60079-26:2007 (3051SFx models with RTD are certified to EN60079-0:2006) II 1/2 G Ex d IIC T6…T4 Ga/Gb, T6(-60 °C ≤ T ≤...
  • Page 16 June 2016 Quick Start Guide IA ATEX FISCO Certificate: BAS01ATEX1303X Standards: EN 60079-0: 2012, EN 60079-11: 2012 II 1 G Ex ia IIC T4 Ga, T4(-60 °C ≤ T ≤ +70 °C) Markings: FISCO Voltage U 17.5 V Current I 380 mA Power P 5.32 W...
  • Page 17 Quick Start Guide June 2016 7.7 International E7 IECEx Flameproof and Dust Certificate: IECEx KEM 08.0010X (Flameproof) Standards: IEC 60079-0:2011, IEC 60079-1: 2007, IEC 60079-26:2006 (3051SFx models with RTD are certified to IEC 60079-0:2004) Markings: Ex d IIC T6…T4 Ga/Gb, T6(-60 °C ≤ T ≤...
  • Page 18 June 2016 Quick Start Guide Special Conditions for Safe Use (X): 1. The Model 3051S Transmitters fitted with transient protection are not capable of withstanding the 500 V test as defined in Clause 6.3.13 of EN 60079-11:2012. This must be taken into account during installation. 2.
  • Page 19 Quick Start Guide June 2016 2. The terminal pins of the Model 3051S SuperModule must be provided with a degree of protection of at least IP20 in accordance with IEC/EN 60529. 3. The Model 3051S enclosure may be made of aluminum alloy and given a protective polyurethane paint finish;...
  • Page 20 June 2016 Quick Start Guide I2 INMETRO Intrinsic Safety Certificate: CEPEL 05.0722X [Mfg USA, Singapore, Germany], CEPEL 07.1414X [Mfg Brazil] Standards: ABNT NBR IEC 60079-0:2008, ABNT NBR IEC 60079-11:2009, ABNT NBR IEC 60079-26:2008, ABNT NBR IEC 60529:2009 Markings: Ex ia IIC T4 Ga, T4(-20 °C ≤ T ≤...
  • Page 21 Quick Start Guide June 2016 7.9 China E3 China Flameproof and Dust Ignition-proof Certificate: 3051S: GYJ111400X [Mfg USA, China, Singapore] 3051SFx: GYJ11.1711X [Mfg USA, China, Singapore] 3051S-ERS: GYJ101345X [Mfg USA, China, Singapore] Standards: 3051S: GB3836.1-2000, GB3836.2-2000, GB12476.1-2000 3051SFx: GB3836.1-2010, GB3836.2-2010, GB3836.20-2010, GB12476.1-2000 3051S-ERS: GB3836.1-2000, GB3836.2-2000 Markings: 3051S: Ex d IIC T5/T6;...
  • Page 22 June 2016 Quick Start Guide I3 China Intrinsic Safety Certificate: 3051S: GYJ111401X [Mfg USA, China, Singapore] 3051SFx: GYJ11.1707X [Mfg USA, China, Singapore] 3051S-ERS: GYJ111265X [Mfg USA, China, Singapore] Standards: 3051S: GB3836.1-2000, GB3836.4-2000 3051SFx: GB3836.1/4-2010, GB3836.20-2010, GB12476.1-2000 3051S-ERS: GB3836.1-2000, GB3836.4-2000 Markings: 3051S, 3051SFx: Ex ia IIC T 3051S-ERS: Ex ia IIC T4 Special Conditions for Safe Use (X): 1.
  • Page 23 Quick Start Guide June 2016 N3 China Type n Certificate: 3051S: GYJ101112X [Mfg China] 3051SF: GYJ101125X [Mfg China] Standards: GB3836.1-2000, GB3836.8-2003 Markings: Ex nL IIC T5 Special Conditions for Safe Use (X): 1. Symbol “X” is used to denote specific conditions of use: The apparatus is not capable of withstanding the 500 V test to earth for one minute.
  • Page 24 June 2016 Quick Start Guide GB3836.16-2006 “Electrical apparatus for explosive gas atmospheres Part 16: Inspection and maintenance of electrical installation (other than mines)” GB50257-1996 “Code for construction and acceptance of electric device for explosion atmospheres and fire hazard electrical equipment installation engineering”. 7.10 EAC - Belarus, Kazakhstan, Russia EM Technical Regulation Customs Union (EAC) Flameproof Certificate: RU C-US.GB05.B.00835...
  • Page 25 Quick Start Guide June 2016 7.14 Additional Certifications SBS American Bureau of Shipping (ABS) Type Approval Certificate: 00-HS145383-6-PDA Intended Use: Measure gauge or absolute pressure of liquid, gas or vapor applications on ABS classed vessels, marine, and offshore installations. ABS Rules: 2013 Steel Vessels Rules 1-1-4/7.7, 1-1-A3, 4-8-3/1.7, 4-8-3/1.11.1, 4-8-3/13.1 SBV Bureau Veritas (BV) Type Approval...
  • Page 26 June 2016 Quick Start Guide Figure 7. Rosemount 3051S Declaration of Conformity...
  • Page 27 Quick Start Guide June 2016...
  • Page 28 June 2016 Quick Start Guide...
  • Page 29 Quick Start Guide June 2016...
  • Page 30 June 2016 Quick Start Guide...
  • Page 31 Quick Start Guide June 2016 Rosemount 3051S China RoHS List of Rosemount 3051S Parts with China RoHS Concentration above MCVs / Hazardous Substances Hexavalent Polybrominated Polybrominated Part Name Lead Mercury Cadmium Chromium biphenyls diphenyl ethers (Pb) (Hg) (Cd) (Cr +6) (PBB) (PBDE) Electronics...
  • Page 32 +65 6777 8211 Standard Terms and Conditions of Sale can be found at www.Emerson.com/en-us/pages/Terms-of-Use.aspx +65 6777 0947 The Emerson logo is a trademark and service mark of Emerson Enquiries@AP.EmersonProcess.com Electric Co. DeltaV, PlantWeb, SuperModule, Rosemount, and Rosemount Middle East and Africa Regional Office logotype are trademarks of Emerson Process Management.