6.7.6.2

Load monitoring

The load monitoring comprises the following components:
● Load failure monitoring
● Monitoring for torque deviation
● Speed deviation monitoring
If the load monitoring detects a load failure, the inverter issues fault F07936. For a torque
and speed deviation, as response, you can either set an alarm or a fault. Details are
provided in the following descriptions.
Settings
Table 6- 35
Parameters
p2193
Converter with control units CU240D-2
Operating Instructions, 07/2016, FW V4.7 SP6, A5E34262100B AD
Setting options for load monitoring
Description
Load monitoring configuration (factory setting: 1)
0: Monitoring deactivated
1: Torque and load failure monitoring
2: Speed and load failure monitoring
3: Load failure monitoring
Advanced commissioning
6.7 Application-specific functions
211