Summary of Contents for Endress+Hauser Proline Promass E 100
Page 1
Products Solutions Services BA01711D/06/EN/03.21 71506065 2021-01-01 Valid as of version 01.03.zz (Device firmware) Operating Instructions Proline Promass E 100 Coriolis flowmeter Modbus RS485...
Page 2
• The manufacturer reserves the right to modify technical data without prior notice. Your Endress+Hauser Sales Center will supply you with current information and updates to these instructions. Endress+Hauser...
Proline Promass E 100 Modbus RS485 About this document About this document Document function These Operating Instructions contain all the information that is required in various phases of the life cycle of the device: from product identification, incoming acceptance and storage, to mounting, connection, operation and commissioning through to troubleshooting, maintenance and disposal.
• W@M Device Viewer (www.endress.com/deviceviewer): Enter the serial number from nameplate • Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the 2D matrix code (QR code) on the nameplate Detailed list of the individual documents along with the documentation code →...
Proline Promass E 100 Modbus RS485 About this document 1.3.1 Standard documentation Document type Purpose and content of the document Technical Information Planning aid for your device The document contains all the technical data on the device and provides an overview of the accessories and other products that can be ordered for the device.
Safety instructions Proline Promass E 100 Modbus RS485 Safety instructions Requirements for the personnel The personnel for installation, commissioning, diagnostics and maintenance must fulfill the following requirements: ‣ Trained, qualified specialists must have a relevant qualification for this specific function and task.
Verification for borderline cases: ‣ For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of fluid-wetted materials, but does not accept any warranty or liability as minute changes in the temperature, concentration or level of contamination in the process can alter the corrosion resistance properties.
It meets general safety standards and legal requirements. It also complies with the EU directives listed in the device-specific EU Declaration of Conformity. Endress+Hauser confirms this by affixing the CE mark to the device.
Proline Promass E 100 Modbus RS485 Product description Product description The device consists of a transmitter and a sensor. The Safety Barrier Promass 100 is part of the scope of supply and must be implemented to operate the device. The device is available as a compact version: The transmitter and sensor form a mechanical unit.
Is the envelope present with accompanying documents? • If one of the conditions is not satisfied, contact your Endress+Hauser Sales Center. • Depending on the device version, the CD-ROM might not be part of the delivery! The Technical Documentation is available via the Internet or via the Endress+Hauser Operations App, see the "Product identification"...
7 sections • The W@M Device Viewer: enter the serial number from the nameplate (www.endress.com/deviceviewer) • The Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the 2-D matrix code (QR code) on the nameplate. 4.2.1...
Page 14
Incoming acceptance and product identification Proline Promass E 100 Modbus RS485 Date: A0029207 4 Example of a sensor nameplate, part 2 Approval information for explosion protection, Pressure Equipment Directive and degree of protection Permitted ambient temperature (T Document number of safety-related supplementary documentation...
Proline Promass E 100 Modbus RS485 Incoming acceptance and product identification 4.2.3 Promass 100 safety barrier nameplate Safe area NON intrinsically safe circuit (grey terminals) Promass 100 Safety Barrier Intrinsically safe circuits (blue terminals) HAZARDOUS area A0017854 5 Example of a Promass 100 safety barrier nameplate Non-hazardous area or Zone 2/Div.
Storage and transport Proline Promass E 100 Modbus RS485 Storage and transport Storage conditions Observe the following notes for storage: ‣ Store in the original packaging to ensure protection from shock. ‣ Do not remove protective covers or protective caps installed on process connections.
Proline Promass E 100 Modbus RS485 Storage and transport 5.2.2 Measuring devices with lifting lugs CAUTION Special transportation instructions for devices with lifting lugs ‣ Only use the lifting lugs fitted on the device or flanges to transport the device.
Installation Proline Promass E 100 Modbus RS485 Installation Installation conditions 6.1.1 Mounting position Mounting location A0028772 To prevent measuring errors arising from accumulation of gas bubbles in the measuring tube, avoid the following mounting locations in the pipe: • Highest point of a pipeline.
Page 19
Proline Promass E 100 Modbus RS485 Installation Ø orifice plate, pipe restriction [mm] [in] [mm] [in] ³⁄₈ 0.24 ½ 0.40 0.55 1½ 0.87 1.10 1.97 Orientation The direction of the arrow on the sensor nameplate helps you to install the sensor according to the flow direction (direction of medium flow through the piping).
Installation Proline Promass E 100 Modbus RS485 Inlet and outlet runs No special precautions need to be taken for fittings which create turbulence, such as valves, elbows or T-pieces, as long as no cavitation occurs → 20. A0029322 A0029323 Installation dimensions For the dimensions and installation lengths of the device, see the "Technical...
Proline Promass E 100 Modbus RS485 Installation NOTICE Electronics overheating on account of thermal insulation! ‣ Recommended orientation: horizontal orientation, transmitter housing pointing downwards. ‣ Do not insulate the transmitter housing . ‣ Maximum permissible temperature at the lower end of the transmitter housing: 80 °C (176 °F)
Installation Proline Promass E 100 Modbus RS485 Sanitary compatibility When installing in hygienic applications, please refer to the information in the "Certificates and approvals/hygienic compatibility" section → 99 Rupture disk Information that is relevant to the process: → 93.
Proline Promass E 100 Modbus RS485 Installation 6.2.2 Preparing the measuring device 1. Remove all remaining transport packaging. 2. Remove any protective covers or protective caps present from the sensor. 3. If present, remove transport protection of the rupture disk.
Electrical connection Proline Promass E 100 Modbus RS485 Electrical connection NOTICE The measuring device does not have an internal circuit breaker. ‣ For this reason, assign the measuring device a switch or power-circuit breaker so that the power supply line can be easily disconnected from the mains.
Proline Promass E 100 Modbus RS485 Electrical connection Connecting cable between Safety Barrier Promass 100 and measuring device Cable type Shielded twisted-pair cable with 2x2 wires. When grounding the cable shield, observe the grounding concept of the plant. Maximum cable resistance 2.5 Ω, one side Comply with the maximum cable resistance specifications to ensure the operational reliability of the measuring device.
Page 26
Electrical connection Proline Promass E 100 Modbus RS485 Connection methods available Order code Possible options for order code Power "Housing" "Electrical connection" Output supply Options Device plugs Device plugs Option Q: 2 x plug M12x1 A, B, C → 28 →...
Page 27
Proline Promass E 100 Modbus RS485 Electrical connection 72 A A0030219 10 Modbus RS485 terminal assignment, connection version for use in intrinsically safe areas (connection via Safety Barrier Promass 100) Intrinsically safe power supply Modbus RS485 Order code 10 (L+)
Proline Promass E 100 Modbus RS485 Electrical connection 7.2.5 Shielding and grounding Shielding and grounding concept 1. Maintain electromagnetic compatibility (EMC). 2. Take explosion protection into consideration. 3. Pay attention to the protection of persons. 4. Comply with national installation regulations and guidelines.
Electrical connection Proline Promass E 100 Modbus RS485 7.3.1 Connecting the transmitter The connection of the transmitter depends on the following order codes: • Housing version: compact or ultra-compact • Connection version: device plug or terminals A0016924 12 Housing versions and connection versions...
Proline Promass E 100 Modbus RS485 Electrical connection For device version with device plug: follow step 6 only. 1. Depending on the housing version, loosen the securing clamp or fixing screw of the housing cover. 2. Depending on the housing version, unscrew or open the housing cover.
Electrical connection Proline Promass E 100 Modbus RS485 7.3.3 Ensuring potential equalization Requirements No special measures for potential equalization are required. For devices intended for use in hazardous locations, please observe the guidelines in the Ex documentation (XA). Special connection instructions 7.4.1...
Electrical connection Proline Promass E 100 Modbus RS485 If the transmitter is used in the intrinsically safe area 220 Ω A0030217 18 Terminating resistor can be enabled via DIP switch in the Safety Barrier Promass 100 Ensuring the degree of protection The measuring device fulfills all the requirements for degree of protection IP66/67, Type 4X enclosure.
Page 35
Proline Promass E 100 Modbus RS485 Electrical connection Depending on the device version: are all the device plugs firmly tightened → 30? • Does the supply voltage match the specifications on the transmitter nameplate → 86? • For device version with Modbus RS485 intrinsically safe: does the supply voltage match the ...
Operation options Proline Promass E 100 Modbus RS485 Operation options Overview of operating options A0017760 Computer with "FieldCare" or "DeviceCare" operating tool via Commubox FXA291 and service interface Control system (e.g. PLC) Endress+Hauser...
Proline Promass E 100 Modbus RS485 Operation options Structure and function of the operating menu 8.2.1 Structure of the operating menu For an overview of the operating menu for experts: "Description of Device Parameters" document supplied with the device→ 101...
Operation options Proline Promass E 100 Modbus RS485 8.2.2 Operating philosophy The individual parts of the operating menu are assigned to certain user roles (operator, maintenance etc.). Each user role contains typical tasks within the device lifecycle. Menu/parameter User role and tasks...
Page 39
Proline Promass E 100 Modbus RS485 Operation options X X X X X X X 1120.50 kg/h A0037831 Operational display Device tag→ 57 Status area Display area for measured values (4-line) Status area The following symbols appear in the status area of the operational display at the top right: •...
Operation options Proline Promass E 100 Modbus RS485 Totalizer The measurement channel number indicates which of the three totalizers is displayed. Output Measurement channel numbers Symbol Meaning Measurement channel 1 to 4 The measurement channel number is displayed only if more than one channel is present for the same measured variable type (e.g.
Computer with "FieldCare" operating tool with "CDI Communication FXA291" COM DTM Via service interface (CDI) A0014019 Service interface (CDI = Endress+Hauser Common Data Interface) of the measuring device Commubox FXA291 Computer with FieldCare operating tool with COM DTM CDI Communication FXA291 8.4.2...
Page 42
Operation options Proline Promass E 100 Modbus RS485 Access is via: CDI service interface → 41 Typical functions: • Configuring parameters of transmitters • Loading and saving device data (upload/download) • Documentation of the measuring point • Visualization of the measured value memory (line recorder) and event logbook...
DeviceCare Function scope Tool to connect and configure Endress+Hauser field devices. The fastest way to configure Endress+Hauser field devices is with the dedicated "DeviceCare" tool. Together with the device type managers (DTMs) it presents a convenient, comprehensive solution. For details, see Innovation Brochure IN01047S Source for device description files See information →...
System integration Proline Promass E 100 Modbus RS485 System integration Overview of device description files 9.1.1 Current version data for the device Firmware version 01.03.zz • On the title page of the Operating Instructions • On the transmitter nameplate • Firmware version Diagnostics →...
Proline Promass E 100 Modbus RS485 System integration Code Name Description Application Write single Master writes a new value to one Write only 1 device parameter registers Modbus register of the measuring Example: reset totalizer device. Use function code 16 to write multiple registers with just 1 telegram.
System integration Proline Promass E 100 Modbus RS485 INTEGER Data length = 2 bytes (1 register) Byte 1 Byte 0 Most significant byte (MSB) Least significant byte (LSB) STRING Data length = depends on the device parameter, e.g. presentation of a device parameter with a data length = 18...
Page 48
System integration Proline Promass E 100 Modbus RS485 Configuring the scan list via Modbus RS485 Carried out using register addresses 5001 - 5016 Scan list Modbus RS485 register Data type Configuration register 5001 Integer Scan list register 0 Integer 5016...
Proline Promass E 100 Modbus RS485 Commissioning Commissioning 10.1 Function check Before commissioning the device, make sure that the post-installation and post- connection checks have been performed. • "Post-mounting check" checklist → 23 • "Post-connection check" checklist → 34 10.2...
Page 50
Commissioning Proline Promass E 100 Modbus RS485 Temperature unit Pressure unit Parameter overview with brief description Parameter Description Selection/ Factory setting User entry Mass flow unit Select the unit for mass flow. Unit choose list Country-dependent: • kg/h Result • lb/min The selected unit applies for: •...
Page 51
Proline Promass E 100 Modbus RS485 Commissioning Parameter Description Selection/ Factory setting User entry Temperature unit Select the unit for temperature. Unit choose list Country-dependent: • °C (Celsius) Result • °F (Fahrenheit) The selected unit applies for: • Output • Reference temperature •...
Commissioning Proline Promass E 100 Modbus RS485 10.3.2 Selecting and setting the medium The Medium selection submenu contains parameters that have to be configured for selecting and setting the medium. Navigation path "Setup" menu → Medium selection Structure of the submenu Medium selection →...
Proline Promass E 100 Modbus RS485 Commissioning 10.3.3 Configuring communication interface The Communication submenu guides you systematically through all parameters that must be configured for selecting and setting the communication interface. Navigation path "Setup" menu → Communication Structure of the submenu Communication →...
Page 54
Commissioning Proline Promass E 100 Modbus RS485 Selection/ Parameter Description Factory setting User entry Assign diagnostic Select diagnostic behavior • Off Alarm behavior for MODBUS • Alarm or warning communication. • Warning • Alarm Failure mode Select measured value • NaN value...
Proline Promass E 100 Modbus RS485 Commissioning 10.3.4 Configuring the low flow cut off The Low flow cut off submenu contains parameters that have to be set for configuring the low flow cut off. Navigation path "Setup" menu → Low flow cut off...
Commissioning Proline Promass E 100 Modbus RS485 10.3.5 Configuring the partial filled pipe detection The Partially filled pipe detection submenu contains parameters that have to be set for configuring empty pipe detection. Navigation path "Setup" menu → Partial filled pipe detection...
Proline Promass E 100 Modbus RS485 Commissioning 10.4 Advanced settings The Advanced setup menu with its submenus contains all parameters needed for specific settings. Navigation path "Setup" menu → Advanced setup Overview of the parameters and submenus in the "Advanced setup" menu taking the...
Proline Promass E 100 Modbus RS485 Commissioning Progress Parameter overview with brief description Parameter Description Selection/ Factory setting User entry Installation direction Change the sign of the direction • Flow in arrow direction Flow in arrow of flow of the fluid.
Commissioning Proline Promass E 100 Modbus RS485 Selection/ Parameter Prerequisite Description Factory setting User entry Volume unit The following option Select the unit for Unit choose list Country-dependent is selected in the volume. • l Assign process • gal (us)
Proline Promass E 100 Modbus RS485 Commissioning 10.5.1 Parameter overview with brief description Selection/ Parameter Prerequisite Description Factory setting User entry Assign simulation Select a process • Off process variable variable for the • Mass flow simulation process • Volume flow that is activated.
Page 62
Commissioning Proline Promass E 100 Modbus RS485 4 - Bus termination 3 - Not used 2 - Not used 1 - Write protection A0017954 1. Depending on the housing version, loosen the securing clamp or fixing screw of the housing cover.
Proline Promass E 100 Modbus RS485 Operation Operation 11.1 Read device locking status The write protection types that are currently active can be determined using the Locking status parameter. Navigation path "Display/operation" menu → Locking status Function scope of "Locking status" parameter...
Operation Proline Promass E 100 Modbus RS485 Parameter overview with brief description Parameter overview with brief description Parameter Prerequisite Description Display Mass flow – Displays the mass flow currently Floating-point number with measured sign Volume flow – Displays the volume flow currently...
Proline Promass E 100 Modbus RS485 Operation Parameter overview with brief description Parameter Prerequisite Description Display Totalizer value 1-3 One of the following Displays the current Floating point number options is selected in the totalizer counter value. with sign Assign process variable...
Page 66
Operation Proline Promass E 100 Modbus RS485 "Operation" submenu Operation → Control totalizer 1 Preset value 1 Control totalizer 2 Preset value 2 Control totalizer 3 Preset value 3 Reset all totalizers Parameter overview with brief description Selection/ Parameter Prerequisite...
Proline Promass E 100 Modbus RS485 Diagnostics and troubleshooting Diagnostics and troubleshooting 12.1 General troubleshooting For output signals Problem Possible causes Remedy Green power LED on the main Supply voltage does not match that Apply the correct supply voltage electronics module of the specified on the nameplate.
Diagnostics and troubleshooting Proline Promass E 100 Modbus RS485 Alarm Device status is ok. Flashing red A device error of diagnostic behavior "Warning" has occurred. • A device error of diagnostic behavior "Alarm" has occurred. • Boot loader is active.
Proline Promass E 100 Modbus RS485 Diagnostics and troubleshooting Status signals The status signals provide information on the state and reliability of the device by categorizing the cause of the diagnostic information (diagnostic event). Symbol Meaning Failure A device error has occurred. The measured value is no longer valid.
Diagnostics and troubleshooting Proline Promass E 100 Modbus RS485 • Via register address 6821 (data type = string): diagnosis code, e.g. F270 • Via register address 6859 (data type = integer): diagnosis number, e.g. 270 For an overview of diagnostic events with diagnosis number and diagnosis code →...
Proline Promass E 100 Modbus RS485 Diagnostics and troubleshooting 12.6 Overview of diagnostic information The amount of diagnostic information increases if the measuring device has one or more application packages. Diagnostics for the sensor Status Diagnostic Diagnosti signal Short text...
Page 72
Diagnostics and troubleshooting Proline Promass E 100 Modbus RS485 Diagnostics for the configuration Status Diagnostic Diagnosti signal Short text Remedial measures behavior c number from the from the factory factory Data transfer 1. Check connection. Alarm 2. Retry data transfer.
Proline Promass E 100 Modbus RS485 Diagnostics and troubleshooting Status Diagnostic Diagnosti signal Short text Remedial measures behavior c number from the from the factory factory Inhomogeneous Oscillation amplitude limit! Alarm* The fluid properties do not allow a precise measurement.
Diagnostics and troubleshooting Proline Promass E 100 Modbus RS485 12.9 Event logbook 12.9.1 Event history A chronological overview of the event messages that have occurred is provided in the events list which contains a maximum of 20 message entries. This list can be displayed via FieldCare if necessary.
Proline Promass E 100 Modbus RS485 Diagnostics and troubleshooting Information event Event text I1151 History reset I1209 Density adjustment OK I1221 Zero point adjust failure I1222 Zero point adjustment OK 12.10 Resetting the measuring device Using the Device reset parameter it is possible to reset the entire device configuration or some of the configuration to a defined state.
"Manufacturer' s information" document. The manufacturer' s information is available: • In the Download Area of the Endress+Hauser Internet site: www.endress.com → Download • Specify the following details: •...
→ 92. 13.2 Measuring and test equipment Endress+Hauser offers a wide variety of measuring and test equipment, such as W@M or device tests. Your Endress+Hauser Sales Center can provide detailed information on the services. List of some of the measuring and testing equipment: → 80→ 81 13.3...
• The measuring devices have a modular design. • Spare parts are grouped into logical kits with the associated Installation Instructions. • Repairs are carried out by Endress+Hauser Service or by appropriately trained customers. • Certified devices can only be converted to other certified devices by Endress+Hauser Service or at the factory.
(WEEE), the product is marked with the depicted symbol in order to minimize the disposal of WEEE as unsorted municipal waste. Do not dispose of products bearing this marking as unsorted municipal waste. Instead, return them to Endress+Hauser for disposal under the applicable conditions.
Various accessories, which can be ordered with the device or subsequently from Endress +Hauser, are available for the device. Detailed information on the order code in question is available from your local Endress+Hauser sales center or on the product page of the Endress+Hauser website: www.endress.com.
Tool to connect and configure Endress+Hauser field devices. Innovation brochure IN01047S Commubox FXA291 Connects Endress+Hauser field devices with a CDI interface (= Endress +Hauser Common Data Interface) and the USB port of a computer or laptop. Technical Information TI00405C 15.4...
Technical data Proline Promass E 100 Modbus RS485 Technical data 16.1 Application The measuring device is intended only for the flow measurement of liquids and gases. Depending on the version ordered, the measuring device can also measure potentially explosive, flammable, poisonous and oxidizing media.
Proline Promass E 100 Modbus RS485 Technical data 16.3 Input Measured variable Direct measured variables • Mass flow • Density • Temperature Calculated measured variables • Volume flow • Corrected volume flow • Reference density Measuring range Measuring ranges for liquids Measuring range full scale values ...
• Operating pressure to increase accuracy (Endress+Hauser recommends the use of a pressure measuring device for absolute pressure, e.g. Cerabar M or Cerabar S) •...
Page 85
Proline Promass E 100 Modbus RS485 Technical data Interface/protocol • Via digital communication: Modbus RS485 • Via service interface CDI-RJ45 service interface Plain text display With information on cause and remedial measures Light emitting diodes (LED) Status information Status indicated by various light emitting diodes The following information is displayed depending on the device version: •...
Technical data Proline Promass E 100 Modbus RS485 16.5 Power supply Terminal assignment • → 26 • → 25 Pin assignment, device plug → 28 Supply voltage The power unit must be tested to ensure it meets safety requirements (e.g. PELV, SELV).
Proline Promass E 100 Modbus RS485 Technical data Power supply failure • Totalizers stop at the last value measured. • Depending on the device version, the configuration is retained in the device memoryor in the pluggable data memory (HistoROM DAT).
Page 88
Technical data Proline Promass E 100 Modbus RS485 Temperature ±0.5 °C ± 0.005 · T °C (±0.9 °F ± 0.003 · (T – 32) °F) Zero point stability Zero point stability [mm] [in] [kg/h] [lb/min] ³⁄₈ 0.20 0.007 ½ 0.65 0.024...
Page 89
Proline Promass E 100 Modbus RS485 Technical data Base repeatability Design fundamentals → 90 Mass flow and volume flow (liquids) ±0.075 % o.r. ±0.05 % o.r. (calibration option, for mass flow) Mass flow (gases) ±0.35 % o.r. Density (liquids) ±0.00025 g/cm...
Page 90
Technical data Proline Promass E 100 Modbus RS485 o.r. = of reading It is possible to compensate for the effect by: • Reading in the current pressure measured value via the current input. • Specifying a fixed value for the pressure in the device parameters.
Proline Promass E 100 Modbus RS485 Technical data Example for maximum measured error E [%] 95 100 Q [%] A0030289 Maximum measured error in % o.r. (example) Flow rate in % of maximum full scale value 16.7 Installation Installation conditions →...
Technical data Proline Promass E 100 Modbus RS485 Shock resistance Shock, half-sine according to IEC 60068-2-27 6 ms 30 g Shock resistance Shock due to rough handling following IEC 60068-2-31 Interior cleaning • SIP cleaning • CIP cleaning Electromagnetic • As per IEC/EN 61326 and NAMUR Recommendation 21 (NE 21) compatibility (EMC) •...
Page 93
Proline Promass E 100 Modbus RS485 Technical data Sensor housing The sensor housing is filled with dry nitrogen gas and protects the electronics and mechanics inside. If a measuring tube fails (e.g. due to process characteristics like corrosive or abrasive fluids), the fluid will initially be contained by the sensor housing.
Page 94
Technical data Proline Promass E 100 Modbus RS485 • The minimum recommended full scale value is approx. 1/20 of the maximum full scale value • In most applications, 20 to 50 % of the maximum full scale value can be considered ideal •...
Proline Promass E 100 Modbus RS485 Technical data 16.10 Mechanical construction Design, dimensions For the dimensions and installation lengths of the device, see the "Technical Information" document, "Mechanical construction" section. Weight All values (weight exclusive of packaging material) refer to devices with EN/DIN PN 40 flanges.
Page 96
Technical data Proline Promass E 100 Modbus RS485 Cable entries/cable glands A0020640 22 Possible cable entries/cable glands Female thread M20 × 1.5 Cable gland M20 × 1.5 Adapter for cable entry with female thread G ½" or NPT ½"...
Proline Promass E 100 Modbus RS485 Technical data Process connections • Flanges according to EN 1092-1 (DIN2501) / according to ASME B 16.5 / as per JIS B2220: Stainless steel, 1.4404 (F316/F316L) • All other process connections: Stainless steel, 1.4404 (316/316L) Available process connections→...
The device meets the legal requirements of the applicable EU Directives. These are listed in the corresponding EU Declaration of Conformity along with the standards applied. Endress+Hauser confirms successful testing of the device by affixing to it the CE mark. RCM-tick symbol The measuring system meets the EMC requirements of the "Australian Communications...
Page 99
• With the identification PED/G1/x (x = category) on the sensor nameplate, Directive Endress+Hauser confirms conformity with the "Essential Safety Requirements" specified in Appendix I of the Pressure Equipment Directive 2014/68/EU. • Devices not bearing this marking (PED) are designed and manufactured according to good engineering practice.
The application packages can be ordered with the device or subsequently from Endress+Hauser. Detailed information on the order code in question is available from your local Endress+Hauser sales center or on the product page of the Endress+Hauser website: www.endress.com.
For an overview of the scope of the associated Technical Documentation, refer to the following: • W@M Device Viewer (www.endress.com/deviceviewer): Enter the serial number from nameplate • Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the 2D matrix code (QR code) on the nameplate Standard documentation Brief Operating Instructions...
Page 102
Technical data Proline Promass E 100 Modbus RS485 Supplementary device- Safety Instructions dependent documentation Content Documentation code ATEX/IECEx Ex i XA00159D ATEX/IECEx Ex nA XA01029D cCSAus IS XA00160D INMETRO Ex i XA01219D INMETRO Ex nA XA01220D Special Documentation Content Documentation code...