Front Panel Lcd Selection And - Tripp Lite SmartOnline AG-0358 Series Owner's Manual

Single-phase rack-mount online ups with built-in lcd monitoring & control screen
Table of Contents

Advertisement

Available languages

Available languages

  • ENGLISH, page 1
Operations
Front Panel LCD Selection and Configuration Options
MAIN MENU / SUBMENU
STATUS
Load Status
In/Out Status
Energy Status
Battery Status
Power Flow Chart
CONTROL
Start Batt. Test
Reset Fault State
Auto Batt. Testing
EVENT LOG
On Batt. Events
All Events
SETTINGS
Basic setup
DISPLAY / SETTING OPTIONS
• Load level (%, kW, kVA, A, PF)
• Available capacity (%, kW, kVA)
• Input voltage & frequency (Vac, Hz)
• Output voltage & frequency (Vac, Hz)
• Load Group 1 (On, Off)
• Load Group 2 (On, Off)
• Load Group 3 (On, Off)
• Efficiency (%)
• Avg. Power (kw/hr.)
• Configured power strategy
• Battery model & serial number
• Installed (mm/dd/yyyy)
• Expires (mm/dd/yyyy)
• View UPS operational flow chart
• Initiates a manual battery test
• Resets any fault state messages
• Set regular battery self-test interval
o Disable
o 4 weeks (factory setting)
o 13 weeks
o 26 weeks
• Event counter
(UPS On-battery events only)
• Total minutes (total minutes of
on-battery mode operation)
• Most recent power failure (date)
• Months until battery replacement alert
(months)
• Event details (date, time &
description for the last 20 logged events)
• Event counter (all events)
• Most recent event (date)
• Date time log
System
• Current date (display, set date)
• Current time (display, set time)
• Audible alarm (enable, disable)
• Language (select)
Output voltage
• 200
• 208
• 220
• 230
• 240
DISPLAY / SETTING DESCRIPTION
UPS load percent (%), kilowatt (kW), kilovoltamp
(kVA), amp (A) & power factor (PF).
UPS capacity available in percent (%), kilowatts (kW)
& kilovoltamps (kVA).
Displays UPS input and output status information for input / output
voltage (Vac), frequency (Hz) and outlet group power status (On/
Off) information.
Displays UPS efficiency percentage (%), connected equipment
kilowatt hour consumption (kw/hr.) and configured power strategy.
Displays Battery Pack model number & serial number (Tripp Lite
SMART BATTERY PACKS) only, installation date and user configured
expiration date.
Displays UPS operating mode in a graphical flow chart.
Initiates a momentary UPS battery self-test with immediate Pass/
Fail results.
Use this option to clear UPS fault messages.
Use this option to initiate automatic UPS battery testing at regular
intervals.
Displays a summary of all ON-BATTERY events where the UPS
switched to battery mode in response to a protected condition.
Event details lists the last 20 battery events. As additional alerts
occur, the oldest records will be automatically removed.
Displays a summary of all Recorded events. Event details lists the
last 20 events. As additional alerts occur, the oldest records will
be automatically removed.
Displays, sets and resets date, time, audible alarm status and
language settings.
Note: Audible Alarm DISABLE setting prevents power fail and
operating fault alarms only, the UPS will always "beep" to confirm
the UPS is accepting user input from the front-panel LCD
navigation buttons.
Note: The current date and current local time are reported directly
from the remote management card.
Use the SETTINGS / BASIC / OUTPUT VOLTAGE option to display or
set the nominal UPS output voltage (changes take effect on next
restart).
21

Advertisement

Table of Contents
loading

Table of Contents