Technical specifications
6.1 Technical specifications
Article number
•
Number of operating cycles, max.
Switching capacity of contacts
with inductive load, max.
–
with resistive load, max.
–
Thermal continuous current, max.
–
Switching current, min.
–
Rated switching voltage (DC)
–
Rated switching voltage (AC)
–
Cable length
•
shielded, max.
•
unshielded, max.
Interrupts/diagnostics/status information
Diagnostics function
Substitute values connectable
Alarms
•
Diagnostic alarm
Diagnostic messages
•
Monitoring the supply voltage
•
Wire-break
•
Short-circuit
•
Group error
Diagnostics indication LED
Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
•
•
Channel status display
•
for channel diagnostics
•
for module diagnostics
Potential separation
Potential separation channels
•
between the channels
•
between the channels and backplane bus
•
between the channels and the power sup-
ply of the electronics
Permissible potential difference
between channels and backplane bus/supply
voltage
Isolation
Isolation tested with
24
6ES7132-6MD00-0BB1
7 000 000; see additional description in the man-
ual
2 A; see additional description in the manual
5 A; see additional description in the manual
5 A
100 mA; 5 V DC
24 V DC to 120 V DC
24V AC to 230V AC
1 000 m
200 m
Yes
Yes
Yes
Yes
No
No
Yes
Yes; green LED
No
Yes; green/red DIAG LED
Yes
Yes
Yes
240 V AC
2 500 V DC (type test)
Digital output module RQ 4x120VDC-230VAC/5A NO MA ST (6ES7132-6MD00-0BB1)
Equipment Manual, , A5E36107692-AB