Toggle/jog switch for controlling the relay
You can switch the relay using the toggle/jog switch to jog, MANUAL ON (manual mode) or
automatic mode for each channel. In manual mode, the state set by the output data is
ignored.
The 4 toggle/jog switches are located on the front of the electronic module.
• JOG (switch position "up": job mode): Short-term manual operation (MANUAL ON), while
jogged.
• AUT (switch position "middle" or "not activated": Automatic mode): Each channel is
activated via the user program (normal operation).
• ON (switch position "down": Manual mode (MANUAL ON) permanently): Each channel is
switched on ("1" signal) independent of the activation of the user program (and substitute
values).
Digital output module RQ 4x120VDC-230VAC/5A NO MA ST (6ES7132-6MD00-0BB1)
Equipment Manual, , A5E36107692-AB
3.1 Wiring and block diagram
Wiring