Article number
Input current
Current consumption, max.
Power loss
Power loss, typ.
Address area
Address space per module
•
Inputs
•
Outputs
Hardware configuration
Automatic encoding
•
Mechanical coding element
•
Type of mechanical coding element
Selection of BaseUnit for connection variants
•
2-wire connection
•
3-wire connection
Digital outputs
Type of digital output
Number of digital outputs
Short-circuit protection
Switching frequency
•
with resistive load, max.
•
with inductive load, max.
•
on lamp load, max.
Total current of the outputs
•
Current per channel, max.
•
Current per module, max.
Total current of the outputs (per module)
horizontal installation
up to 50 °C, max.
–
up to 60 °C, max.
–
vertical installation
up to 40 °C, max.
–
up to 50 °C, max.
–
Relay outputs
•
Number of relay outputs
•
Rated supply voltage of relay coil L+ (DC)
•
Current consumption of relays (coil current
of all relays), max.
•
external protection for relay outputs
Digital output module RQ 4x120VDC-230VAC/5A NO MA ST (6ES7132-6MD00-0BB1)
Equipment Manual, , A5E36107692-AB
6ES7132-6MD00-0BB1
100 mA; without load
1.5 W
1 byte; With QI
1 byte
Yes
Yes
type C
BU type B1
BU type B0
Relays
4
No
2 Hz
0.5 Hz
2 Hz
5 A
20 A
20 A
16 A
20 A
16 A
4
24 V
40 mA
Yes, with miniature fuse max. 6 A tripping current
and quick-response tripping characteristic
Technical specifications
6.1 Technical specifications
23