Mode 6 & 7: External Target Temperature Input Operation: Adjust Display - Camus Hydronics DynaFlame DFW501 Installation, Operation And Service Manual

Gas fired commercial copper tube boilers
Hide thumbs Also See for DynaFlame DFW501:
Table of Contents

Advertisement

6.12
MODE 6 & 7: EXTERNAL TARGET TEMPERATURE INPUT OPERATION: ADJUST DISPLAY
From the Home display;
1) Press
Display
simultaneously to view the following parameters:
Parameter
Name
Mode
Differential
Temperature
Pump Delay
Temperature
Units
Parameter Description
Operating mode for the boiler.
NOTE: A complete description of
each mode can be found in
section 8.4 Modes of Operation in
this manual.
To provide a modulation rate
above and below the Boiler
Target temperature. For example,
o
if the value is 10
F and the Boiler
o
Target is 160
F the boiler will
begin to modulate at 155
o
shut off at 165
F.
Boiler post pump time after
burner has shut off, in seconds.
Select the desired unit of
measurement
Parameter Range
1 to 8
Default = 1
o
Au, 2 to 42
F
(Au, -17 to 6
Default = Au
o
F and
OFF, 0:20 to 9:55
min, On
Default = 1:00 min
o
o
F,
C
o
Default =
F
o
C)
38