MODE 6 & 7: EXTERNAL TARGET TEMPERATURE INPUT OPERATION: ADJUST DISPLAY
From the Home display;
1) Press
Display
Parameter
Name
Modulation
Total Run
Time Since
Installation
simultaneously to view the following parameters:
Parameter
Name
Mode
Differential
Temperature
Pump Delay
Temperature
Units
Parameter Description
Real-time modulating output
percentage
Monitors the amount of
operational time since the
MicoFlame was installed. The
first two digits are the number of
thousands of hours and the three
digit display shows the number of
hundreds of hours.
Press
simultaneously to
reset the counter
Parameter Description
Operating mode for the boiler.
NOTE: A complete description of
each mode can be found in
section 8.4 Modes of Operation in
this manual.
To provide a modulation rate
above and below the Boiler
Target temperature. For example,
o
if the value is 10
F and the Boiler
o
Target is 160
F the boiler will
begin to modulate at 155
o
shut off at 165
F.
Boiler post pump time after
burner has shut off, in seconds.
Select the desired unit of
measurement
37
Parameter Range
0 to 100%
Alternates between
00 and 999
Parameter Range
1 to 8
Default = 1
o
Au, 2 to 42
(Au, -17 to 6
Default = Au
o
F and
OFF, 0:20 to 9:55
min, On
Default = 1:00 min
o
o
F,
C
o
Default =
F
F
o
C)