Air Required For Combustion And Ventilation; Exhaust Fans; Outdoor Venting; Thruwall Venting - Camus Hydronics DynaFlame DFW501 Installation, Operation And Service Manual

Gas fired commercial copper tube boilers
Hide thumbs Also See for DynaFlame DFW501:
Table of Contents

Advertisement

2.2.1
AIR REQUIRED FOR COMBUSTION AND
VENTILATION
If air is taken directly from outside the building with no duct,
provide two permanent openings:
a)
Net free area for combustion air opening shall be in
accordance with all applicable codes. In the absence of
such codes provide combustion air opening with a
minimum free area of one square inch per 7000 Btuh
input (5.5 cm per kW) up to 1,000,000 Btuh and one
square inch per 14,000 Btuh in excess of 1.000,000
Btuh. This opening must be ducted no .higher than 18"
nor less than 6" above the floor. Provide a ventilation
air opening located as high as practical in the room
sized no less than 10% of the air supply opening.
b)
Provision for combustion and ventilation must be in
accordance with :
Applicable sections of The National Fuel Gas ode
ANSI Z223.1
Applicable sections of CAN/CGA B149 installation
Codes
Applicable provisions of the local building codes.
Outside air openings shall directly communicate with the
outdoors.
CAUTION
Under no circumstances should the mechanical room ever
be under a negative pressure. Particular care should be
taken where exhaust fan, attic fans, clothes dryers,
compressors, air handling units, etc., may take away air
from the unit.
2.2.2

EXHAUST FANS

Any fan or equipment which exhausts air from the
equipment room may deplete the combustion air supply
and/or cause a downdraft in the venting system through a
barometric damper if installed. Spillage of flue products
from the venting system into an occupied living space can
cause a very hazardous condition that must be immediately
corrected.
2.3

OUTDOOR VENTING

The DynaFlame windproof cabinet protects the unit from
weather, when fitted with the factory supplied air intake and
UL approved vent cap (93-0298), it will be self-venting and
suitable for outdoor installation.
1.
Outdoor models must be installed outdoors and must
use the Air Intake and Vent Cap supplied by Camus
Hydronics.
2.
Periodically check to ensure that air intake and vent
cap are not obstructed.
3.
Locate appliance at least 3 feet away from any
overhang.
4.
Locate appliance at least ten feet from building air
intake.
5.
Avoid installation in areas where runoff from adjacent
building can spill onto appliance.
For outdoor installations, always consider the use of a
shelter such as a garden shed in lieu of direct exposure of
the appliance to the elements. The additional protection
afforded by the shelter will help to minimize nuisance
problems with electrical connections and will allow easier
servicing of the appliance under severe weather conditions.
NOTE
2.4

THRUWALL VENTING

When fitted with the factory supplied vent terminal, the
DynaFlame can vent up to 100 equivalent feet. Elbows can
range from 7 to 19 feet in equivalent length depending on
centreline radius. Refer to table 5 for vent sizes.
Appliances may be installed with either a horizontal
sidewall vent or vertical roof top vent. Terminals differ with
each application. Horizontal lengths over 5 feet must be
installed using corrosion resistant stainless steel. Use
single wall vent and seal all joints or use pressure rated
double wall vent.
When using single wall vent, all vent connector seams and
joints must be sealed with pressure sensitive aluminium
tape or silicone sealant as specified by the vent
manufacturer. Aluminium tape must meet the provisions of
SMACNA AFTS-100-73 Standard.
When venting through unheated spaces, use venting
material which will minimize flue gas condensation inside
the vent. Provisions must be made for collecting and
disposing of any condensation which may occur. The
authorities having jurisdiction must approve venting.
Periodically check to ensure that the vent terminal is
unobstructed.
This venting system uses the appliance's internal
combustion air fan to force the flue products out
horizontally. Vent cap and venting must be listed type
Category IV vent materials.
The DynaFlame fan generates a positive pressure in the
flue. Combustion air is drawn from the equipment room The
THRUWALL termination caps are available from the factory
as a kit. Refer to local codes for proper installation and
location of vent terminals.
2.4.1
THRUWALL VENT CAP (14-0090) THRUWALL
INTAKE AIR CAP (14-0101)
The THRUWALL vent cap kit includes the wall
penetration assembly and the discharge screen
assembly.
The opening through the wall for installation of the
THRUWALL vent cap must provide an air space
clearance of 1 inch (2.5cm) around the flue pipe. The
diameter of the opening for installation of the
THRUWALL vent cap will be 2 inches (5cm) larger
than the nominal diameter of the installed vent pipe to
the THRUWALL vent cap. The diameter of the opening
for the air inlet cap will be the same as the nominal
size of the pipe.
Install the proper vent pipe to the vent cap (provided by
Camus Hydronics).
Follow all requirements in the General Venting sections
for venting flue products to the outdoors.
12

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents