6.2

VARIABLE FREQUENCY DRIVE (VFD)

The VFD has a factory set security code which has to be
entered before any adjustments can be made. The VFD
has 50 parameters, which can be adjusted. At present only
the following are pertinent:
Table 13: Variable Frequency Drive Parameters
Parameter
Function
#
1
High/Low Voltage
Input Voltage 120,
220-240, 460-480
2
Carrier Frequency
4
Stop Method
Standard Speed
5
Source
19
Acceleration Time
20
Deceleration Time
28
Fixed Boost
36
Preset Speed
38
Skip Bandwidth
45
Speed at Minimum
Signal
46
Speed at Maximum
Signal
50
Fault History
51 thru 58
Miscellaneous
29
Settings
01
02
03
03
04 (03 for 2- 10
VDC)
120 sec
60 sec
1.0
29
3.0
• 500 - 3000 Non-
Condensing: 29
or 32
• 500 – 3000 Near-
Condensing: 20-
25
• 500 – 3000
Condensing: 25
• 3500 – 6004 All
Models: 14-18
• All Models: 60
View Only