Mode 3: Dedicated Domestic Hot Water Operation: View Display - Camus Hydronics DynaFlame DFW501 Installation, Operation And Service Manual

Gas fired commercial copper tube boilers
Hide thumbs Also See for DynaFlame DFW501:
Table of Contents

Advertisement

6.7

MODE 3: DEDICATED DOMESTIC HOT WATER OPERATION: VIEW DISPLAY

From the Home display;
1) Press [ITEM] to view the following parameters:
Display
33
Parameter
Parameter Description
Name
To provide a target setpoint for the
Boiler Target
heating system. Setpoint is controlled
Temperature
to the inlet sensor
Boiler Outlet
Real-time Outlet Temperature to Boiler
Temperature
Boiler Inlet
Real-time Inlet Temperature to Boiler
Temperature
Real-time temperature difference
Boiler Delta
between the outlet sensor and the inlet
T
sensor.
DHW
Real-time DHW Temperature
Temperature
Real-time modulating output
Modulation
percentage
Monitors the amount of operational
time since the MicoFlame was
installed. The first two digits are the
Total Run
number of thousands of hours and the
Time Since
three digit display shows the number
Installation
of hundreds of hours.
Press
the counter
simultaneously to reset
Parameter
Range
o
---, 35 to 266
F
o
(---, 2 to 130
C)
o
14 to 266
F
o
(-10 to 130
C)
o
14 to 266
F
o
(-10 to 130
C)
o
-99 to 252
F
o
(-72 to 122
C)
o
14 to 266
F
o
(-10 to 130
C)
0 to 100%
Alternates
between 00 and
999

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents