6.14
MODE 8: EXTERNAL DRIVE OPEATION: ADJUST DISPLAY
From the Home display;
1) Press
Display
6.15
ERROR MESSAGES
Error Message
simultaneously to view the following parameters:
Parameter
Name
Mode
Pump Delay
Temperature
Units
The control was unable to read a piece of information its EEPROM
memory. The control will stop operation until all settings in the Adjust
menu have been checked by the installer.
Outlet Sensor Short Circuit.
If the inlet sensor is operational, the control will operate using the inlet
sensor. Otherwise, the control will not operate the burner.
Test the outlet sensor and related wiring. The error message will clear
once the error condition is corrected and a button is pressed.
Outlet Sensor Open.
If the inlet sensor is operational, the control will operate using the inlet
sensor. Otherwise, the control will not operate the burner.
Test the outlet sensor and related wiring. The error message will clear
once the error condition is corrected and a button is pressed.
Inlet Sensor Short Circuit
The boiler will continue operation.
Test the inlet sensor and related wiring. The error message will clear
once the error condition is corrected and a button is pressed.
Parameter Description
Operating mode for the boiler.
NOTE: A complete description of
each mode can be found in section
8.4 Modes of Operation in this
manual.
Boiler post pump time after burner
has shut off, in seconds.
Select the desired unit of
measurement
Description
Parameter
Range
1 to 8
Default = 1
OFF, 0:20 to 9:55
min, On
Default = 1:00
min
o
o
F,
C
o
Default =
F
40