Electrical Data 30Rqm 160-520; Electrical Data 30Rqp 160-520; Short Circuit Current Withstand Capability - Carrier 30RQM 160 Installation, Operation And Maintenance Instructions

Reversible air-to-water heat pump
Table of Contents

Advertisement

4.3 - Electrical data 30RQM 160-520

30RQM
Power circuit
Nominal voltage
Voltage range
Control circuit supply
Nominal unit current draw
(1)
Circuit A&B
Maximum unit input power
(2)
Circuit A&B
Cosine Phi unit at maximum power
Maximum unit current draw (Un-10%)
Circuit A&B
Maximum unit current draw (Un)
Circuit A&B - Standard Unit
Circuit A&B - Unit with option 231
Maximum start-up current, standard unit (Un)
Circuit A&B
Max. start-up current, unit with soft starter (Un)
Circuit A&B
(1) Conditions equivalent to the standardised Eurovent conditions (evaporator water input-output temperature = 12 °C/7 °C, outside air temperature = 35 °C).
(2) Power input, compressors and fans, at the unit operating limits (saturated suction temperature 15 °C, saturated condensing temperature 68.3 °C) and nominal voltage of 400 V (data given on the
unit nameplate).
(3) Maximum unit operating current at maximum unit power input and at 360 V.
(4) Maximum unit operating current at maximum unit power input and at 400 V (values given on the unit nameplate).
(5) Maximum instantaneous starting current at operating limits (maximum operating current of the smallest compressor(s) + current of the fan(s) + locked rotor current of the largest compressor).
Fan motor electrical data reported upstream of the variable drive at Eurovent equivalent conditions and motor ambient air temperature of 50 °C at 400 V: Current 3.8 A; Start-up current 20 A; Power
input: 1.75 kW.

4.4 - Electrical data 30RQP 160-520

30RQP
Power circuit
Nominal voltage
Voltage range
Control circuit supply
Nominal unit current draw
(1)
Circuit A&B
Cosine Phi unit at maximum power
Circuit A&B
Cosinus Phi unité à puissance maximale
Maximum unit current draw (Un-10%)
Circuit A&B
Maximum unit current draw (Un)
Circuit A&B - Standard Unit
Circuit A&B - Unit with option 231
Maximum start-up current, standard unit (Un)
Circuit A&B
Max. start-up current, unit with soft starter (Un)
Circuit A&B
(1) Conditions equivalent to the standardised Eurovent conditions (evaporator water input-output temperature = 12 °C/7 °C, outside air temperature = 35 °C).
(2) Power input, compressors and fans, at the unit operating limits (saturated suction temperature 15 °C, saturated condensing temperature 68.3 °C) and nominal voltage of 400 V (data given on the
unit nameplate).
(3) Maximum unit operating current at maximum unit power input and at 360 V.
(4) Maximum unit operating current at maximum unit power input and at 400 V (values given on the unit nameplate).
(5) Maximum instantaneous starting current at operating limits (maximum operating current of the smallest compressor(s) + current of the fan(s) + locked rotor current of the largest compressor).
Fan motor electrical data reported upstream of the variable drive at Eurovent equivalent conditions and motor ambient air temperature of 50 °C at 400 V: Current 3.8 A; Start-up current 20 A; Power
input: 1.75 kW.
4.5 - Short circuit stability current
Short circuit stability current (TN system
30RQM/30RQP
Rated Short-Time Withstand Current (Icw), (1s) rms value/peak lpk
Circuits A & B
kA/kA
With fuses upstream - maximum fuse values assigned (gL/gG)
Circuits A & B
A
With fuses upstream - Conditional Short-Circuit Current (Icc)/Icf
Circuits A & B
kA
(1) Type of system earthing
IT system: The short circuit current stability values given above for the TN system are not valid for IT, modifications are required.
160
180
V-ph-Hz 400 - 3 -50
V
360 - 440
24 V via internal transformer
A
100
110
kW
80
88
0,88
0,87
(2)
(3)
A
144
158
(4)
A
133
146
A
100
110
(5)
A
307
356
(5)
A
261
283
160
180
V-ph-Hz
400 - 3 -50
V
360 - 440
24 V via internal transformer
A
97
107
(2)
kW
81
88
0,88
0,88
(2)
(3)
A
142
154
(4)
A
131
142
A
98
108
(5)
A
305
353
(5)
A
259
279
)
(1)
160
180
8/30
8/30
200
200
50
50
210
230
240
270
133
147
151
166
107
118
120
134
0,88
0,88
0,87
0,88
192
211
215
241
177
195
199
222
133
148
151
166
352
406
409
396
305
332
336
350
210
230
240
270
130
144
147
162
108
118
120
134
0,88
0,88
0,88
0,88
189
208
211
237
174
192
195
218
131
146
148
164
349
402
405
392
302
329
332
346
210
230
240
270
8/30
8/30
8/30
8/30
200
250
250
250
50
50
50
50
310
330
380
430
191
199
233
266
152
161
188
215
0,87
0,88
0,88
0,88
273
289
337
385
252
266
310
354
192
200
233
266
462
440
485
529
389
394
438
482
310
330
380
430
186
195
227
260
153
161
188
215
0,88
0,88
0,88
0,88
268
284
331
378
247
261
305
348
188
197
230
262
458
436
479
523
384
389
433
476
310
330
380
430
15/65
15/65
15/65
15/65
315
315
400
400
50
50
50
50
470
520
294
322
236
258
0,88
0,88
422
460
390
425
296
326
600
636
527
562
470
520
288
316
237
259
0,88
0,88
416
454
383
419
291
321
594
629
520
556
470
520
20/80
20/80
630
630
50
50
19