Electrical Data; Wiring; Recommended Connection Method For Power And Communication Wiring - Carrier 38MARBQ12AA1 Service Manual

Outdoor unit single zone ductless system
Hide thumbs Also See for 38MARBQ12AA1:
Table of Contents

Advertisement

ELECTRICAL DATA

SYSTEM SIZE
Volts-PH-Hz
Max – Min*
Oper. Voltage
MCA
Recommended
Fuse Size (in A.)
Max Fuse/
CB AMP
Volts-PH-Hz
RLA
*Permissible limits of the voltage range at which the unit operates satisfactorily.
LEGEND:
FLA - Full Load Amps
MCA - Minimum Circuit Amps
RLA - Rated Load Amps

WIRING

All wires must be sized per NEC (National Electrical Code) or CEC
(Canadian Electrical Code) and local codes. Use Electrical Data table
MCA (minimum circuit amps) and MOCP (maximum over current
protection) to correctly size the wires and the disconnect fuse or
breakers respectively.
Recommended Connection Method for Power
and Communication Wiring:
The main power is supplied to the outdoor unit. The field supplied 14/
3 power/communication wiring, from the outdoor unit to the indoor
unit, consists of four (4) wires and provides the power for the indoor
unit. Two wires are high voltage AC power, one is communication
wiring and the other is a ground wire. Wiring between indoor
and outdoor unit is polarity sensitive. The use of BX wire is NOT
recommended.
If installed in a high Electromagnetic field (EMF) area and
communication issues exists, a 14/2 stranded shielded wire can be
used to replace L2 and (S) between outdoor unit and indoor unit
landing the shield onto ground in the outdoor unit only.
8
Table 5 — Electrical Data
12K
9K
115-1-60
208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
127-104
253-187
19
15
20
15
25
15
115-1-60
208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
11.5
6.0
Specifications subject to change without notice.
12K
18K
253-187
253-187
253-187
15
16
15
20
15
25
8.5
14.25
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage
or improper operation.
Wires should be sized based on NEC and local codes.
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage
or improper operation.
Be sure to comply with local codes while running wire from
the indoor unit to the outdoor unit.
Every wire must be connected firmly. Loose wiring may
cause the terminal to overheat or result in unit malfunction. A
fire hazard may also exist. Ensure all wiring is tightly
connected.
No wire should touch the refrigerant tubing, compressor or
any moving parts.
Disconnecting means must be provided and shall be located
within sight and readily accessible from the air conditioner.
Connecting cable with conduit shall be routed through the
hole in the conduit panel.
NOTE: Matches with multi-family and residential fan coils
require separate power for the indoor and outdoor unit. A 24V
interface kit is required for compatibility. Refer to the 24V
Interface Kit installation manual.
24K
30K
208/230-1-60
253-187
253-187
25
23
25
25
35
30
208/230-1-60
14.8
15
SG-38MARB-01
36K
28
30
35
18