Connecting a Releasing Device to the Addressable Control Module

7.5 Connecting a Releasing Device to the Addressable Control Module
For use with NFS2-3030, NFS2-640, NFS-320(C), and NFS-320SYS
The FCM-1-REL module can control 1 A of current. Make sure to keep total system current within the limits of the power supply. Power
for the module must come from the FACP's main power supply or any UL 864-listed 24 VDC regulated, power-limited power supply for
Fire Protective Signaling. For more information, refer to the Device Compatibility Document. See critical notes below wiring diagrams.
Critical Requirements. When connecting a releasing device to the FCM-1-REL module, note the following:
1.
See Appendix A, "Power Considerations", on page 66 for information on monitoring 24 VDC power.
2.
Do not T-tap or branch a Class B or Class A circuit.
3.
Only one (1) 24V solenoid or two (2) 12V solenoids in series can be connected to the FCM-1-REL.
4.
Do not loop wiring under the screw terminals. Break the wire run to provide supervision of connections.
5.
All applications using the FCM-1-REL are power-limited:
• Program the releasing circuit for Type Code REL CKT ULC or RELEASE CKT.
• Circuits are supervised against opens and shorts.
6.
Refer to your FACP's listing documents for instructions on setting the Soak Timer.
(* For legacy panels, refer to FACP programming manual.)
7.
The FCM-1-REL module must be programmed with the correct releasing type code listed in your FACP's listing documents.
(* For legacy panels, refer to FACP programming manual.)
8.
Manual releasing disconnect switch and monitor module required for UL 864 10th Edition.
Figure 7.6 shows Class B wiring of the FCM-1-REL with a manual releasing disconnect switch. (For use with NFS2-3030, NFS2-640,
NFS-320(C), and NFS-320SYS.) See Installation Document LS10231-000GE-E for MRD-1 wiring.
Non-resettable 24-VDC power supply isolated,
regulated, power limited per NFPA 70, listed
for fire protection with battery backup.
For supervision, see Appendix A.
Module polarities are shown in alarm
condition. All wiring shown is
supervised and power-limited.
Figure 7.6 NFPA Class B Wiring of the FCM-1-REL with MRD-1 Manual Releasing Disconnect Switch and FMM-101
Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021
Compatible UL-listed
24 VDC releasing device.
One (1) device maximum.
MRD-1 Manual Releasing
Disconnect Switch
with ELR
IDC
FCM-1-REL
FMM-101 Programmed to provide
supervisory signal to panel when power is
lost to the releasing device.
SLC (-)
SLC (+)
Control Modules
SLC (-)
SLC (+)
When using the
FCM-1-REL for Class B
applications, remove
jumper J1.
47