Supervising 24 VDC Power
that circuit. The relay can be installed in line with any leg (+ or –) of the supervised NAC or IDC circuit, either a two- or a four-wire
style.
Figure A.1 shows Class B supervision of a 24VDC circuit using the FCM-1 or FZM-1. Refer to the Device Compatibility Document for
compatible notification appliances and relays.
Figure A.2 shows an alternate Class B method of supervising a 24VDC circuit using a control module that is fully powered from the
SLC loop.
Figure A.2 Alternate: 2-Address Method of Supervising a 24 VDC Circuit - Class B
Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021
24 VDC Power from
Control Panel or
Power Supply
Power Supervision
Relay
(EOLR-1)
ELR:
(Use 47K with FCM-1
or 3.9K with FZM-1)
Figure A.1 Supervised 24 VDC Circuit - Class B
ELR 47K
Power Supervision
Relay
(EOLR-1)
Supervised NAC or IDC
ELR 47K
Supervised NAC or IDC
24 VDC Power from
Control Panel or Power Supply
Last device on the SLC loop
(FCM-1 or FZM-1)
FCM-1
FMM-1
Power Considerations
67