Control Modules
Figure 7.7 shows Class A wiring of the FCM-1-REL with a double-pull/single-throw manual releasing disconnect switch. (For use with
NFS2-3030, NFS2-640, NFS-320(C), and NFS-320SYS.) See Installation Document LS10231-000GE-E for MRD-1 wiring.
Non-resettable 24-VDC power supply isolated,
regulated, power limited per NFPA 70, listed
for fire protection with battery backup.
For supervision, see Appendix A.
Module polarities are shown in alarm
condition. All wiring shown is
supervised and power-limited.
Figure 7.7 NFPA Class A Wiring of the FCM-1-REL with MRD-1 Manual Releasing Disconnect Switch and FMM-101
48
Compatible UL-listed
Compatible UL-listed
24 VDC releasing device.
24 VDC releasing device.
One (1) device maximum.
One (1) device maximum.
MRD-1 Manual Releasing
Disconnect Switch
with ELR
IDC
Connecting a Releasing Device to the Addressable Control Module
FCM-1-REL
FMM-101 Programmed to provide
supervisory signal to panel when power is
lost to the releasing device.
Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021
SLC (-)
SLC (+)
SLC (-)
SLC (+)