Unspecified Voltage (Between Indoor Unit And Outdoor Unit) - Daikin FTXG20LV1BW Service Manual

Inverter pair wall mounted type l-series
Hide thumbs Also See for FTXG20LV1BW:
Table of Contents

Advertisement

Troubleshooting
4.10 Unspecified Voltage (Between Indoor Unit and Outdoor
Unit)
UA
Error Code
Method of Error
The supply power is detected for its requirements (pair type is different from multi type) by the
Detection
indoor / outdoor transmission signal.
Error Decision
The pair type and multi type are interconnected.
Conditions
Supposed
Causes
Troubleshooting
Check the
indoor
Check the code numbers
(2P012345, for example) of the
indoor and outdoor unit PCB with
the Parts List.
71
Wrong models interconnected
Wrong wiring of connecting wires
Wrong indoor unit PCB or outdoor unit PCB mounted
Defective indoor unit PCB
Defective outdoor unit PCB
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
combination of the
and outdoor unit.
OK?
YES
Are the
connecting wires connected
property?
YES
Matched compatibly?
YES
NO
NO
NO
SiBE041401E
Match the compatible models.
Correct the connection.
Change for the correct PCB.
Replace the indoor unit PCB
(or the outdoor unit PCB).
(R19506)