Unspecified Voltage (Between Indoor Unit And Outdoor Unit) - Daikin FLKS25BAVMB Service Manual

Inverter pair floor / ceiling suspended dual type flk(x)s-ba series
Hide thumbs Also See for FLKS25BAVMB:
Table of Contents

Advertisement

Troubleshooting
4.9
Unspecified Voltage (Between Indoor Unit and Outdoor
Unit)
UA
Error Code
Method of Error
The supply power is detected for its requirements (pair type is different from multi type) by the
indoor / outdoor transmission signal.
Detection
Error Decision
The pair type and multi type are interconnected.
Conditions
Supposed
Causes
Troubleshooting
Check the
indoor
76
Wrong models interconnected
Wrong wiring of connecting wires
Wrong indoor unit PCB or outdoor unit PCB mounted
Defective indoor unit PCB
Defective outdoor unit PCB
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
combination of the
and outdoor unit.
OK?
YES
Are the
connecting wires connected
property?
YES
NO
NO
SiBE05-722EE
Match the compatible models.
Correct the connection.
Check the code numbers
(2P012345, for example) of the
indoor and outdoor unit PCB
with the Parts List.
If not matched, change for the
correct PCB.
(R20435)