Mechanical And Climatic Ambient Conditions - Siemens SIMATIC S7-1500 System Manual

Automation system
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Technical specifications

16.4 Mechanical and climatic ambient conditions

16.4
Mechanical and climatic ambient conditions
Operating conditions
The S7-1500 automation system is suitable for use in weather-proof, fixed locations. The
operating conditions exceed requirements according to DIN IEC 60721-3-3:
● Class 3M3 (mechanical requirements)
● Class 3K3 (climatic requirements)
Test of mechanical ambient conditions
The table below provides important information with respect to the type and scope of the test
of ambient mechanical conditions.
Table 16- 8
Test of mechanical ambient conditions
Condition tested
Vibration
Shock
Continuous shock
Reduction of vibrations
If your S7-1500 automation system is exposed to severe shock or vibration, take appropriate
measures to reduce the acceleration or the amplitude.
We recommend the installation of the S7-1500 automation system on damping materials (for
example, rubber-bonded-to-metal mounting).
190
Test Standard
Remark
Vibration test
Type of oscillation: Frequency sweeps with a rate of change of
according to
1 octave/minute.
IEC 60068-2-6 (Sinus)
5 Hz ≤ f ≤ 8.4 Hz, constant amplitude 7 mm
8.4 Hz ≤ f ≤ 150 Hz, constant acceleration 2 g
Duration of oscillation: 10 frequency sweeps per axis, along each of the
3 mutually perpendicular axes
Shock, tested
Type of shock: Half-sine
according to
Shock intensity: 15 g max., duration 11 ms
IEC 60068-2-27
Direction of shock: 3 shocks each in (+/-) direction, along each of the
3 mutually perpendicular axes
Shock, tested
Type of shock: Half-sine
according to
Shock intensity: 250 m/s
IEC 60068-2-27
Direction of shock: 1000 shocks each in (+/-) direction, along each of the
3 mutually perpendicular axes
peak value, 6 ms duration
2
S7-1500 Automation System
System Manual, 02/2014, A5E03461182-AB