Commissioning
9.4 Operating modes
Setting the startup behavior
Proceed as follows to set the startup behavior:
1. Select the CPU in the device view of the STEP 7 hardware network editor.
2. In the properties under "General" select the "Startup" area.
Figure 9-3
116
Setting the startup behavior
Sets the startup type after POWER ON
Defines the startup behavior for the case where a module in a slot does not correspond
to the configured module. This parameter applies to the CPU and to all the modules for
which no other setting was selected.
• Startup CPU only if compatible: In this setting a module on a configured slot has to be
compatible with the configured module.
• Startup CPU even if mismatch: At this setting the CPU starts up irrespective of the
type of module plugged.
For locally used modules you can configure the hardware compatibility in the parameter
"Comparison preset to actual module" individually for each slot. When you change the
setting of the hardware compatibility for a module, the setting made at the CPU does not
apply for this module.
Specifies a maximum period (default: 60000 ms) in which the central and distributed I/O
must be ready for operation. The CMs and CPs are supplied with voltage and
communication parameters during the CPU startup. This parameter assignment time
grants a period, within which the I/O modules connected to a CM or CP must be
operationally ready.
The CPU goes into RUN mode when the central and the distributed I/O is operationally
ready within the parameter assignment time.
If the central and distributed I/O is not ready for operation within the configuration time,
the startup characteristics of the CPU depends on the setting of the hardware
compatibility.
S7-1500 Automation System
System Manual, 02/2014, A5E03461182-AB