Set temperature ranges.
Precautions for Safe Use
Do not touch the DIP switch while power is being supplied. Static electricity may cause operating
errors.
Precautions for Correct Use
Precautions for Correct Use
Always turn OFF the power supply before setting the temperature range.
Set the temperature range according to the type of temperature sensor
connected to the Unit.
Temperature data will not be converted correctly if the temperature range
does not match the sensor.
Do not set the temperature range to any values other than those for
which temperature ranges are given in the following table.
An incorrect setting may cause operating errors.
With the Temperature Sensor Unit's DIP switch, set the temperature unit and the temperature
input range.
ON
OFF
SW
1
2
Input type
K
J
Additional Information
Fahrenheit temperature uses the following equation to convert the temperature unit from Celsius,
but the temperature input range is different between Fahrenheit and Celsius.
Fahrenheit temperature (°F) = Celsius temperature (°C) × 1.8 + 32
CP2E CPU Unit Hardware User's Manual(W613)
8 Using Expansion Units and Expansion I/O Units
Setting
Input type
ON
OFF
Temperature unit
ON
OFF
Temperature input
Range (°C)
-200.0 to 1300.0
-100.0 to 850.0
Caution
J
K
°F
°C
Range (°F)
-300.0 to 2300.0
-100.0 to 1500.0