Connecting The Network - Emerson RSTi-OM Quick Start Manual

Master fieldbus module with profinet and modbus/tcp
Hide thumbs Also See for RSTi-OM:
Table of Contents

Advertisement

The arrow points to the switch location. 0 is located at the 9:00 position.
Turn the dial clockwise to the appropriate setting.
3. Close the window and make sure that it snaps shut tightly.
Note: Failure to close the configuration window properly may compromise
IP67 integrity.

Connecting the Network

You can use this procedure to connect the IOLM to the network.
1. Securely connect one end of a shielded twisted-pair (Cat 5 or
higher) M12 Ethernet cable to either Ethernet port.
2. Connect the other end of the cable to the network.
3. Optionally, use the other Ethernet port to daisy-chain to another
Ethernet device.
4. If you did not connect both Ethernet ports, make sure that the
unused port is covered with a connector cap to keep dust and
liquids from getting in the connector.
Note: Ethernet ports must have an approved cable or protective cover
attached to the connector to guarantee IP67 integrity.
12
IO-LINK Master W/ PROFINET and Modbus Quick Start Guide