Setting the Rotary Switch

You can use the rotary switches under the configuration window on the
IOLM to set the lower 3-digits (8 bits) of the static IP address
(192.168.11.XXX).
For example, the default IP address is 192.168.11.202. When the rotary
switches are set to 000, the final segment of the IP address will remain at
202. However, if the rotary switches are changed to 065, then the IOLM
module will obtain the IP address 192.168.11.65
If the rotary switches are set to a non-default position, the upper 9-digits
(24 bits) of the IP address are then taken from the static network address.
The switches only take effect during startup, but the current position is
always shown on the Help | SUPPORT page.
Using the rotary switches to set the IP address may be useful in the
following situations:
A permanent method to assign IP addresses while setting machines
for a special application where a PC or laptop is not available.
A temporary method to assign IP addresses to several IOLMs so that
they do not have duplicate addresses, making IP address
configuration easier when using the web page. After using the web
page to change the IP address, reset the rotary switches back to
000.
10
IO-LINK Master W/ PROFINET and Modbus Quick Start Guide
GFK-3213A