Heat Pump Installation Conditions - Dimplex LIA 0608HWCF M Installation And Operating Instruction

Split air-to-water heat pump with hydrotower compact unit
Table of Contents

Advertisement

English
5.2.1 Wall opening for split lines and
electric wires
Please proceed as follows when laying split lines and electric
wires:
Drill a 70 mm opening for the pipework using a core drill.
The opening for the pipework should be slightly inclined
towards the outdoor unit, so that no rainwater can pene-
trate the building.
Indoor unit
During installation work, please ensure that connection points
are easily accessible for maintenance and repair purposes.
CAUTION!
Care must be taken to ensure that the connections and lines
are not subjected to any mechanical loads.
CAUTION!
Connection lines must not exhibit any mechanical damage.
5.2.2 Wall opening for condensate drain
Outdoor unit
For the safe drainage of the condensate, the condensate drain
must be positioned in such a way that no frost build-up can oc-
cur. The frost line can vary according to the climatic region. The
regulations of the countries in question must be observed.
When laying the condensate connection, pay attention to the
slope that must be maintained.
EN-10
Outdoor unit
Wall
Indoor unit
452172.66.01-EN · FD 0204
LIA 0608HWCF M - LIA 0911HWCF M
5.3 Heat pump installation
conditions:
The refrigerating system described in this manual is filled with
R32. The refrigerant R32 is a colourless, odourless and flamma-
ble gas.
Due to it having a higher density than air, R32 can accumulate
in lower-lying areas without adequate ventilation. At low con-
centrations, symptoms may include dizziness, headache, nau-
sea, and impaired coordination. There is a risk of suffocation at
higher concentrations.
In order to ensure safe operation and, above all, to prevent per-
sonal injury in the event of a leakage, certain criteria apply to the
installation site which must be met in order to minimise possi-
ble hazards to persons, property and the environment.
5.3.1 General installation conditions:
Install the heat pump in rooms with sufficient air circulation
Do not block off any ventilation openings when installing the
heat pump
Do not store or use flammable or combustible substances near
the heat pump
The installation site of the heat pump must not be used as a
workplace or workshop
Do not expose the device to high temperatures, flames, sparks
or sources of ignition (e.g. electric radiator).
The device must not be installed or operated near a naked
flame, gas-powered devices, electric heaters or any other com-
parable source of ignition.
During installation, ensure that the system is easily accessible
for maintenance and repair purposes
The minimum amount of space for the installation room must
be observed depending on the filling quantity of the system
(see cap. 5.3.4 on page 12 Minimum room volume)
CAUTION!
The minimum amount of space for the room must also be
observed when storing the heat pump.