11.2.4 Creating start programs for JOG operation

Setting item
Inching movement
[Cd.16]
amount
[Cd.17] JOG speed
: Refer to Section 5.7 "List of control data" for details on the setting details.
Signal name
PLC READY signal
READY signal
All axis servo ON
Synchronization flag
Interface
Axis stop signal
signal
Start complete signal
BUSY signal
Error detection signal
M code ON signal
Forced stop input signal
Stop signal
External
signal
Upper limit (FLS)
Lower limit (RLS)
: If the PLC CPU is set to the asynchronous mode in the synchronization setting, this must be inserted in the
program for interlocking. If it is set to the synchronous mode, it must not be inserted in the program for
interlocking because it is turned ON when the PLC CPU executes calculation.
A sequence program must be created to execute a JOG operation. Consider the
"required control data setting", "start conditions" and "start time chart" when creating
the program.
The following shows an example when a JOG operation is started for axis 1. ("[Cd.17]
JOG speed" is set to "100.00mm/min" in the example shown.)
Required control data setting
The control data shown below must be set to execute a JOG operation. The
setting is carried out with the sequence program.
Setting
value
0
Set "0".
Set a value equal to or below the "[Pr.31]
10000
JOG speed limit value".
Start conditions
The following conditions must be fulfilled when starting. The required conditions
must also be assembled in the sequence program, and the sequence program
must be configured so the operation will not start if the conditions are not fulfilled.
ON PLC CPU preparation completed
ON QD77GF preparation completed
ON All axis servo ON
ON
OFF Axis stop signal is OFF
OFF Start complete signal is OFF
OFF QD77GF is not operating
OFF There is no error
OFF M code ON signal is OFF
ON There is no forced stop input
OFF Stop signal is OFF
ON Within limit range
ON Within limit range
Setting details
Signal state
QD77GF buffer memory
The access is possible.
11 - 10
Chapter 11 Manual Control
Buffer memory address
4317+100n
4318+100n
4319+100n
n: Axis No.-1
Device
Y0
X0
Y1
X1
[Cd.180] Axis stop
[Md.31] Status: b14
X10 to X1F
[Md.31] Status: b13
[Md.31] Status: b12

Advertisement