Digital Inputs; Digital Outputs - Trane Arctic PolyTherm TP Series Installation, Operation And Maintenance Manual

Simultaneous chiller/heater
Table of Contents

Advertisement

O O p p e e r r a a t t i i n n g g P P r r o o c c e e d d u u r r e e s s

Digital Inputs

Digital input (DI) data includes these parameters:
Digital LEDs
Figure 21. Digital inputs
DI1 Remote On/Off
This activates a module on or off via digital input. If the
primary digital on-off input is enabled, toggling the D D I I 1 1
on the primary module will turn the entire chiller/heater
on or off.
DI2, DI3, and DI4
These show the states of the evaporator, condenser, or
source flow switches. If the digital input for a switch
indicates closed, flow is present. If the digital input for
a switch indicates open, flow is absent.
DI7 and D8
These show the discharge and suction pressure
switches. If the digital input for a switch indicates
closed, the pressure is in the normal range. If the digital
input for a switch indicates open, the pressure is
exceeding normal range threshold (that is, faulty state).
DI9 Phase Monitor
This is feedback for the three-phase power supply
protection feature. If the digital input for this switch
indicates closed, there are no power supply issues. If
the digital input for this switch indicates open, a power
supply failure has been detected.
If the primary phase monitor is enabled, the common
power supply protection module is active for the
chiller/heater. Failure of the phase monitor will affect
42
There is an LED for each digital input that indicates its
current state. For all inputs, the color of the LED
signifies its current state:
G G r r e e e e n n L L E E D D — This digital input is energized, the
connected device is closed.
G G r r a a y y L L E E D D — This digital input is de-energized, the
connected device is open.
all modules in the chiller/heater. In this case, digital
input is optional for the secondary modules.

Digital Outputs

There is an LED for each digital output which shows its
current state.
DO1, DO2 Comp On/Off
This digital output turns a compressor on and off.
DO3 Liq Line Solenoid 'E'
This digital output energizes and de-energizes the
liquid line solenoid valve 'E'.
DO4 Liq Line Solenoid 'S'
This digital output energizes and de-energizes the
liquid line solenoid valve S.
DO6, DO7, DO8, DO9
Valve D1, D2, S1, S2. Used to command refrigerant
valves open / closed. Green LED - valve is commanded
open. Grey LED - valve is commanded closed.
DO10 General Alarm
This digital output energizes when any of the following
alarms occur:
An alarm that shuts down and locks out
compressor 1 or 2.
ARTC-SVX005B-EN