Trane Arctic PolyTherm TP Series Installation, Operation And Maintenance Manual page 81

Simultaneous chiller/heater
Table of Contents

Advertisement

Table 18. Touchscreen interface active alarm states (continued)
Alarm
EVD SYSTEM ALARM
EVD DRIVER A ALARM
EVD DRIVER B ALARM
EVAPORATOR FREEZING ALARM
SOURCE FREEZING ALARM
PHASE MONITOR ALARM
EVAPORATOR FLOW ALARM
CONDENSOR FLOW ALARM
SOURCE FLOW ALARM
CONDENSOR LWT TOO LOW
EVAPORATOR LWT TOO HIGH
HP ALARM
HP SWITCH ALARM
LP ALARM
LP Lockout ALARM
ERROR IN THE NUMBER OF RETAIN
MEMORY WRITINGS
ERROR in RETAIN MEMORY WRITINGS
WRONG TEMPERATURE CONTROL
PARAMETERS
WRONG LOCAL ROTATION CONTROL
PARAMETERS
PRIMARY COMMUNICATION LOST
INCOMPLETE SAFETY CYCLE
cpCOe #2 OFFLINE ALARM
cpCOe #2 WRONG CONFIG ALARM
Valve D1 OPENING FAILURE
Valve D1 CLOSING FAILURE
Valve D2 OPENING FAILURE
Valve D2 CLOSING FAILURE
Valve S1 OPENING FAILURE
Valve S1 CLOSING FAILURE
Valve S2 OPENING FAILURE
Valve S2 CLOSING FAILURE
ARTC-SVX005B-EN
Application
Primary / Secondary
Auto Reset
Primary / Secondary
Auto Reset
Primary / Secondary
Auto Reset
Primary / Secondary
Operator Reset
Primary / Secondary
Operator Reset
Primary / Secondary
Auto Reset
Primary / Secondary
Operator Reset
Primary / Secondary
Operator Reset
Primary / Secondary
Operator Reset
Primary / Secondary
Auto Reset
Primary / Secondary
Auto Reset
Primary / Secondary
Operator Reset
Primary / Secondary
Auto Reset
Primary / Secondary
Operator Reset
Primary / Secondary
Operator Reset
Primary / Secondary
Operator Reset
Primary / Secondary
Operator Reset
Primary / Secondary
Auto Reset
Primary / Secondary
Auto Reset
Secondary
Auto Reset
Primary / Secondary
Auto Reset
Primary / Secondary
Auto Reset
Primary / Secondary
Auto Reset
Primary / Secondary
Operator Reset
Primary / Secondary
Operator Reset
Primary / Secondary
Operator Reset
Primary / Secondary
Operator Reset
Primary / Secondary
Operator Reset
Primary / Secondary
Operator Reset
Primary / Secondary
Operator Reset
Primary / Secondary
Operator Reset
Type
Warning
Warning
Warning
Locks out module
Locks out module
Locks out module
Locks out module
Locks out module
Locks out module
Warning
Warning
Locks out module
Locks out module
Shuts down module
Locks out module
Warning
Warning
Warning
Warning
Switches secondary module to stand-alone mode
Warning
Switches primary and secondary modules in stand-
alone mode
Locks out module
Locks out module
Locks out module
Locks out module
Locks out module
Locks out module
Locks out module
Locks out module
Locks out module
A A c c t t i i v v e e A A l l a a r r m m L L i i s s t t
Action
C–3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Arctic polytherm tm series

Table of Contents