Trane Arctic PolyTherm TP Series Installation, Operation And Maintenance Manual page 69

Simultaneous chiller/heater
Table of Contents

Advertisement

12. Symptom: Compressor thermal protector switch open (overloading)
Possible Causes
Liquid floodback
Compressors overamping
13. Symptom: No low voltage (24 Vac)
Possible Causes
Control circuit fuse open
Phase monitor opened or tripped
No primary voltage on T1 or T2
14. Symptom: Flow switch open
Possible Causes
Insufficient water flow
Switch defective
15. Symptom: Electronic expansion valve superheat too high
Possible Causes
Water/glycol temperature too warm
Obstructed filter dryer
Low refrigerant charge
Improperly set superheat valve setting
16. Symptom: Electronic expansion valve superheat too low
Possible Causes
Suction temperature sensor not properly located
Improperly set superheat valve setting
Low flow
17. Symptom: Contactor/relay inoperative
Possible Causes
Coil shorted or open
Mechanical parts broken or jammed
Coil shorted or open
Contacts broken or jammed
Contacts pitted or burned
No 24 Vac to coil
Bad relay on microprocessor controller
Temperature set point too low
ARTC-SVX005B-EN
C C h h i i l l l l e e r r / / H H e e a a t t e e r r T T r r o o u u b b l l e e s s h h o o o o t t i i n n g g
Potential Solutions
Adjust electronic expansion valve, increase flow, or raise set point
Correct refrigerant charge; check electrical connections
Potential Solutions
Check fuse prong contact points; replace fuse
Replace transformer, T1 or T2 primary or secondary fuse blown
Check breakers, fuses; check power supply specifications
Potential Solutions
Check strainer for debris; clean strainer
Replace flow switch
Potential Solutions
Low refrigerant level; adjust chiller/heater refrigerant charge as
required
Replace filter dryer
Adjust refrigerant as per data plate
Reset valve settings to factory specifications
Potential Solutions
Check if secured to pipe or insulated; check sensor position on pipe at
4-8-10-2 o'clock positions
Reset valve settings to factory specifications
Increase flow or clean strainer
Potential Solutions
Replace contactor
Replace assembly
Replace contactor
Replace contactor
Replace contactor
Check for loose wiring. Replace secondary fuse to T2 transformer
Replace microprocessor controller
Reset above freezing temperature at evaporator or discharge
69