Lennox SLP99UHV Series Unit Information page 55

Hide thumbs Also See for SLP99UHV Series:
Table of Contents

Advertisement

Details of Intake and Exhaust Piping Terminations for
Direct Vent Installations
NOTE - In Direct Vent installations, combustion air is taken
from outdoors and flue gases are discharged to outdoors.
NOTE - Flue gas may be slightly acidic and may adverse-
ly affect some building materials. If any vent termination
is used and the flue gasses may impinge on the building
material, a corrosion-resistant shield (minimum 24 inches
square) should be used to protect the wall surface. If the
optional tee is used, the protective shield is recommend-
ed. The shield should be constructed using wood, plastic,
shee metal or other suitable material. All seams, joints,
cracks, etc. in the affected area should be sealed using an
appropriate sealant. See FIGURE 33.
Intake and exhaust pipes may be routed either horizontal-
ly through an outside wall or vertically through the roof. In
attic or closet installations, vertical termination through the
roof is preferred. FIGURE 31 through FIGURE 39 show
typical terminations.
1 - Intake and exhaust terminations are not required
to be in the same pressure zone. You may exit the
intake on one side of the structure and the exhaust
on another side (FIGURE 32). You may exit the
exhaust out the roof and the intake out the side of
the structure (FIGURE 32).
2 - Intake and exhaust pipes should be placed as close
together as possible at termination end (refer to
illustrations). Maximum separation is 3" (76mm)
on roof terminations and 6" (152mm) on side wall
terminations.
NOTE - When venting in different pressure zones,
the maximum separation requirement of intake and
exhaust pipe DOES NOT apply.
Conditioned
Space
Conditioned
Space
FIGURE 29
Page 55
Pipe Insulation
Unconditioned
Space
3 - On roof terminations, the intake piping should
terminate straight down using two 90° elbows (See
FIGURE 30).
4 - Exhaust piping must terminate straight out or up as
shown. A reducer may be required on the exhaust
piping at the point where it exits the structure to
improve the velocity of exhaust away from the
intake piping. See TABLE 26.
NOTE - Care must be taken to avoid recirculation of
exhaust back into intake pipe.
TABLE 26
EXHAUST PIPE TERMINATION SIZE REDUCTION
SLP99UHV Model
*070
*090
110
135
*SLP99UH-070 and -090 units with the flush-mount termination must use the
1-1/2"accelerator supplied with the kit.
5 - On field-supplied terminations for side wall exit,
exhaust piping may extend a maximum of 12 inches
(305mm) for 2" PVC and 20 inches (508mm) for 3"
(76mm) PVC beyond the outside wall. Intake piping
should be as short as possible. See FIGURE 34.
6 - On field-supplied terminations, a minimum distance
between the end of the exhaust pipe and the end of
the intake pipe without a termination elbow is 8" and
a minimum distance of 6" with a termination elbow.
See FIGURE 34.
Exhaust
Pipe
Intake
Pipe
Termination Pipe Size
1-1/2"
2"
2"
2"

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents