Lennox SLP99UHV Series Unit Information page 17

Hide thumbs Also See for SLP99UHV Series:
Table of Contents

Advertisement

BLO WER DATA
SLP99UH135XV60D BLOWER PERFORMANCE (less filter)
BOTTOM RETURN AIR
HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range
Heating Adjust CFM Selections
Increase (+15%) Heat CFM
Increase (+7.5%) Heat CFM
Default Heat CFM
Decrease (-7.5% ) Heat CFM
Decrease (-15% ) Heat CFM
COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range
Cooling Adjust CFM
Selections
Increase (+10%) Cool CFM
Default Cool CFM
Decrease (-10%) Cool CFM
The effect of static pressure is included in air volumes shown.
The following control configurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between.
Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times.
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages.
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan speeds are approximately 28% and 38% (DIP switch selectable) of the same second-stage COOL speed position.
minimum 380 cfm.
Lennox iHarmony
Zoning System Applications - Minimum blower speed is 450 cfm.
®
35%
40%
949
1033
879
957
808
881
748
817
687
753
First Stage Cool Speed - cfm
Low
Medium-
Medium
Low
High
1070
1260
1410
980
1115
1255
865
1020
1115
Page 17
Heating Input Range and Blower Volume - CFM
50%
60%
1200
1367
1113
1269
1026
1172
956
1095
886
1019
Blower Speed Selections
High
Low
(Default)
1555
1565
1430
1445
1280
1290
70%
80%
90%
1534
1701
1868
1426
1582
1738
1317
1463
1608
1235
1374
1513
1152
1284
1417
Second Stage Cool Speed - cfm
Medium-
Medium
Low
High
1750
1970
1615
1805
1470
1650
100%
2035
1895
1754
1652
1550
High
(Default)
2190
1985
1805

Hide quick links: