III-PLACEMENT AND INSTALLATION
All pipe, fittings, primer and solvent cement must conform
with American National Standard Institute and the Ameri-
can Society for Testing and Materials (ANSI/ASTM) stan-
dards. The solvent shall be free-flowing and contain no
lumps, undissolved particles or any foreign matter that ad-
versely affects the joint strength or chemical resistance of
the cement. The cement shall show no gelation, stratifica-
tion, or separation that cannot be removed by stirring. Re-
fer to TABLE 21 for approved piping and fitting materials.
TABLE 21
PIPING AND FITTINGS SPECIFICATIONS
Schedule 40 PVC (Pipe)
Schedule 40 PVC (Cellular Core Pipe)
Schedule 40 PVC (Fittings)
Schedule 40 CPVC (Pipe)
Schedule 40 CPVC (Fittings)
SDR-21 PVC or SDR-26 PVC (Pipe)
SDR-21 CPVC or SDR-26 CPVC (Pipe)
Schedule 40 ABS Cellular Core DWV
(Pipe)
Schedule 40 ABS (Pipe)
Schedule 40 ABS (Fittings)
ABS-DWV (Drain Waste & Vent) (Pipe &
Fittings)
PVC-DWV (Drain Waste & Vent) Pipe &
Fittings)
PRIMER & SOLVENT CEMENT
PVC & CPVC Primer
PVC Solvent Cement
CPVC Solvent Cement
ABS Solvent Cement
PVC/CPVC/ABS All Purpose Cement
For Fittings & Pipe of the same material
ABS to PVC or CPVC Transition Solvent
Cement
CANADA PIPE & FITTING & SOLVENT
CEMENT
PVC & CPVC Pipe and Fittings
PVC & CPVC Solvent Cement
ABS to PVC or CPVC Transition
Cement
POLYPROPYLENE VENTING SYSTEM
PolyPro® by Duravent
InnoFlue® by Centrotherm
UL 1738 CERTIFIED GAS VENTING SYSTEM
IPEX System1738 Schedule 40 PVC
Pipes and Fittings
IPEX System1738 PVC FGV Cement &
Primer
Solvent cements for plastic pipe are flammable liquids
and should be kept away from all sources of ignition.
Do not use excessive amounts of solvent cement when
making joints. Good ventilation should be maintained to
reduce fire hazard and to minimize breathing of solvent
vapors. Avoid contact of cement with skin and eyes.
Fumes from PVC glue may ignite during system check.
Allow fumes to dissipate for at least 5 minutes before
D1785
placing unit into operation.
F891
D2466
F441
SLP99UHV exhaust and intake connections are made
F438
of PVC. Use PVC primer and solvent cement when
using PVC vent pipe. When using ABS vent pipe, use
D2241
transitional solvent cement to make connections to the
F442
PVC fittings in the unit.
F628
Use PVC primer and solvent cement or ABS solvent ce-
D1527
ment meeting ASTM specifications, refer to TABLE 21.
D2468
As an alternate, use all purpose cement, to bond ABS,
PVC, or CPVC pipe when using fittings and pipe made of
D2661
the same materials. Use transition solvent cement when
bonding ABS to either PVC or CPVC.
D2665
Low temperature solvent cement is recommended. Metal
or plastic strapping may be used for vent pipe hangers.
ASTM
SPECIFICATION
Uniformly apply a liberal coat of PVC primer for PVC
F656
D2564
F493
D2235
D2564, D2235,
F493
D3188
MARKING
ULCS636
UL1738