Lennox SLP99UHV Series Unit Information page 14

Hide thumbs Also See for SLP99UHV Series:
Table of Contents

Advertisement

BLO WER DATA
SLP99UH090XV60C BLOWER PERFORMANCE (less filter)
SINGLE SIDE RETURN AIR − Air volumes in bold require Optional Return Air Base and field fabricated transition to accommodate
20 x 25 x 1 in. air filter in order to maintain proper air velocity.
HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range
Heating Adjust CFM Selections
Increase (+15%) Heat CFM
Increase (+7.5%) Heat CFM
Default Heat CFM
Decrease (-7.5% ) Heat CFM
Decrease (-15% ) Heat CFM
COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range
Cooling Adjust CFM
Selections
Increase (+10%) Cool CFM
Default Cool CFM
Decrease (-10%) Cool CFM
The effect of static pressure is included in air volumes shown.
The following control configurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between.
Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times.
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages.
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan speeds are approximately 28% and 38% (DIP switch selectable) of the same second-stage COOL speed position.
minimum 380 cfm.
Lennox iHarmony
Zoning System Applications - Minimum blower speed is 450 cfm.
®
35%
40%
609
684
551
623
492
562
436
502
380
441
First Stage Cool Speed - cfm
Low
Medium-
Medium
Low
High
1040
1225
1380
960
1085
1225
840
990
1085
Page 14
Heating Input Range and Blower Volume - CFM
50%
60%
835
986
769
914
702
842
633
765
564
687
Blower Speed Selections
High
Low
(Default)
1550
1555
1415
1430
1250
1280
70%
80%
90%
1136
1287
1437
1059
1205
1350
983
1123
1263
896
1028
1159
810
932
1055
Second Stage Cool Speed - cfm
Medium-
Medium
Low
High
1920
1715
1565
1790
1450
1580
100%
1588
1496
1403
1291
1178
High
(Default)
2135
1980
1790

Hide quick links: