2 Specifications
Item
Ethernet
Baud rate
communi-
Physical layer
cations
Frame length
specifica-
tions
Media access method
Modulation
Topology
Transmission media
Maximum transmission distance
between Ethernet switch and
node
Maximum number of cascade
connections
EtherNet/IP
tag data link
(cyclic commu-
*3
nications)
EtherNet/IP
CIP message
*3
service
EtherNet/IP conformance test
USB port
Physical layer
Transmission distance
*1.
A ring topology is available with PMAC firmware revision version 2.7.0 or later.
*2.
Always use shielded cables for EtherNet/IP communications.
*3.
EtherNet/IP is available only for targets and not available for originators.
EtherNet/IP is available only for PMAC firmware revision version 2.6.0 or later whose date of production is September
25th, 2020 or later (Lot number 25920 and later).
Use Power PMAC IDE Ver.4.4.1 or a later version.
*4.
Represents Packet Per Second and indicates the number of sent or received packets that can be processed in a sec-
ond.
2-4
CK3E-1210
1Gbps/100Mbps
1000BASE-T/100BASE-TX
1,514 bytes max.
CSMA/CD
Baseband
Star
Twisted-pair cable of category 5, 5e, or higher (shielded cable)
100m
There are no restrictions if an Ethernet switch is used.
Number of
32
connections
Requested
1 to 1,000 ms
Packet Inter-
(0.5ms units)
val (RPI)
Allowed com-
*4
3,200 pps
munications
bandwidth per
Unit
IO connection
Input: 504 bytes max.
size
Output: 504 bytes max.
UCMM (un-
Number of servers that can perform communications simultaneously:
connected
32
message)
CT17 compliant
USB 3.0 compliant, type A connector. Output voltage: 5 V, 0.9 A max.
3 m max.
CK3E-series Programmable Multi-Axis Controller User's Manual Hardware (I610)
Specifications
CK3E-1310
CK3E-1410
*2