Installing and Connecting the HP 600/610 External Power Supplies
Installation Procedures

Installation Precautions:

Follow these precautions when installing your HP 600 RPS/EPS or
HP 610 EPS:
W A R N I N G S
C a u t i o n s
2-4
The rack or cabinet should be adequately secured to prevent it
from becoming unstable and/or falling over.
Devices installed in a rack or cabinet should be mounted as low as
possible, with the heaviest devices at the bottom and progressively
lighter devices installed above.
Do not use power cord, part number 8120-5337 or 8120-5342, with
the HP 610 EPS. A power cord with a minimum wire gauge of
14 Awg is required to prevent overloading of the power cord. (This
applies to voltages of less than 127 volts.)
Make sure the power source circuits are properly grounded, then use the
power cord supplied with the unit to connect it to the power source.
If your installation requires a different power cord than the one supplied
with the unit, be sure to use a power cord displaying the mark of the safety
agency that defines the regulations for power cords in your country. The
mark is your assurance the power cord can be used safely with the unit.
When installing the unit, note that the AC outlet should be near the unit
and should be easily accessible in case the unit must be powered off.
Ensure the unit does not overload the power circuits, wiring, and over-
current protection. To determine the possibility of overloading the supply
circuits, add together the ampere ratings of all devices installed on the
same circuit as the unit and compare the total with the rating limit for the
circuit. The maximum ampere ratings are usually printed on devices near
the AC power connectors.
Do not install the unit in an environment where the operating ambient
temperature might exceed 55°C (131°F) for the HP 600 RPS/EPS or 50°C
(122°F) for the HP 610 EPS.
Make sure the air flow around the sides and back of the unit is not
restricted. If this unit is placed in a fully enclosed rack, make certain the
ambient temperature inside the rack near the unit does not exceed 55°C
(131°F) for the HP 600 RPS/EPS or 50°C (122°F) for the HP 610 EPS.