Keltron 95M3158 Tones Transmitter Module - Honeywell SILENT KNIGHT SK-5208 Installation And Operation Manual

Fire control/communicator
Table of Contents

Advertisement

Model SK-5208 Fire Control/Communicator Installation and Operation Manual

3.15.2 Keltron 95M3158 Tones Transmitter Module

This section of the manual shows the specific connections you will make when wiring the SK-
5208 to the Keltron 95M3158 Tones Transmitter Module (3158). Refer to the installation
sheet shipped with the 95M3158 for complete information. (Note: The 3158 is not available
from Silent Knight.)
Note: The 3158 Keltron Module must be mounted within 3 feet of the control panel and all wiring must be run in
conduit. The Keltron Module shall be enclosed in the TBX1 enclosure.
1. Wire the 3158 to the SK-5208 as shown in the Figure 3-28.
2. Program NAC 4 for Direct Connect (see Section 4.2.4).
3. Program NAC 3 for Supervisory (see Section 4.2.4).
4. Program NACs 3 and 4 as unsupervised (NACs With EOL). See Section 4.2.4.
5. Program NAC 3 cadence as Steady (see Section 4.2.3).
Figure 3-28 Wiring the Keltron 3158 to the SK-5208
3-38
Trouble Contacts Supervised For
Opens and Ground Faults
Note: The term FACP Term. refers to terminals on the SK-5208
firealarmresources.com
See Table 3-4 for electrical
ratings.
All Other Circuits Supervised
Power Limited
P/N 151204