Clearances

The clearances listed below are minimum distances unless otherwise stated.
A major cause of chimney-related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this
fireplace and flue system be installed only in accordance with these instructions.
• The top, back and sides of the fireplace are defined by
standoffs. The metal ends of the standoff may NOT be
recessed into combustible construction.
Clearance:
A: Mantel Height (min.)
B: Sidewall (on one side)
C: Ceiling (room and/or alcove)
D: Mantel Depth (max.)
E: Alcove Width
F: Alcove Depth
G: From Floor
Note:
D
A
G
Dimension
254 mm
Top of fireplace opening/hot air outlet
152 mm
Side of fireplace opening/hot air outlet
1162 mm
Top of fireplace opening/hot air outlet
730 mm above fireplace opening/hot air
305 mm
outlet
1524 mm
Sidewall to sidewall (minimum)
914 mm
Front to back wall (maximum)
617 mm
Top of fireplace opening/hot air outlet
O
No hearth required
F
B
E
Installed Close
to Floor
F
• If these clearances (air space) to combustible
materials are not adhered to. It is of greatest
importance that this fireplace and flue system be
installed only in accordance with these instructions.
Measured From:
E
Alcove
installation
Fire hazard is an extreme risk
Flue Clearances to Combustibles
Horizontal - Top
Horizontal - Side
Horizontal - Bottom
Vertical
Installed close
to ceiling.
Greenfire® GF1500L-2 Gas Fireplace
76mm
51mm
51mm
51mm
|
9