Hitachi SJ700-4000HFU2 Instruction Manual page 210

Hide thumbs Also See for SJ700-4000HFU2:
Table of Contents

Advertisement

Chapter 4
(6) List of registers
The "R/W" column of the list indicates whether the coils and registers are read-only or readable and writable.
"R" indicates a read-only coil or register. "R/W" indicates a readable and writable coil or register.
(i) List of coils
Coil No.
0000h
(Reserved)
0001h
Operation command
0002h
Rotation direction command
0003h
External trip (EXT)
0004h
Trip reset (RS)
0005h
(Reserved)
0006h
(Reserved)
0007h
Intelligent input terminal [1]
0008h
Intelligent input terminal [2]
0009h
Intelligent input terminal [3]
000Ah
Intelligent input terminal [4]
000Bh
Intelligent input terminal [5]
000Ch
Intelligent input terminal [6]
000Dh
Intelligent input terminal [7]
000Eh
Intelligent input terminal [8]
000Fh
Operation status
0010h
Rotation direction
0011h
Inverter ready
0012h
Unused
0013h
RUN (running)
0014h
FA1 (constant-speed reached)
0015h
FA2 (set frequency overreached)
0016h
OL (overload notice advance signal (1))
0017h
OD (output deviation for PID control)
0018h
AL (alarm signal)
0019h
FA3 (set frequency reached)
001Ah
OTQ (over-torque)
001Bh
IP (instantaneous power failure)
001Ch
UV (undervoltage)
001Dh
TRQ (torque limited)
001Eh
RNT (operation time over)
001Fh
ONT (plug-in time over)
0020h
THM (thermal alarm signal)
0021h
(Reserved)
0022h
(Reserved)
0023h
(Reserved)
0024h
(Reserved)
0025h
(Reserved)
0026h
BRK (brake release)
0027h
BER (brake error)
0028h
ZS (0 Hz detection signal)
0029h
DSE (speed deviation maximum)
002Ah
POK (positioning completed)
002Bh
FA4 (set frequency overreached 2)
002Ch
FA5 (set frequency reached 2)
002Dh
OL2 (overload notice advance signal (2))
002Eh
Odc: Analog O disconnection detection
002Fh
OIDc: Analog OI disconnection detection
0030h
O2Dc: Analog O2 disconnection detection
0031h
(Reserved)
0032h
FBV (PID feedback comparison)
0033h
NDc (communication train disconnection)
0034h
LOG1 (logical operation result 1)
Item
R/W
-
R/W
R/W
R/W
R/W
-
-
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
-
-
-
-
-
R
R
R
R
R
R
R
R
-
-
-
-
R
R
R
Explanation of Functions
1: Run, 0: Stop (valid when A002 = 03)
1: Reverse rotation, 0: Forward rotation (valid when A002 = 03)
1: Trip
1: Reset
1: ON, 0: OFF (*1)
1: ON, 0: OFF (*1)
1: ON, 0: OFF (*1)
1: ON, 0: OFF (*1)
1: ON, 0: OFF (*1)
1: ON, 0: OFF (*1)
1: ON, 0: OFF (*1)
1: ON, 0: OFF (*1)
1: Run, 0: Stop (interlocked to "d003")
1: Reverse rotation, 0: Forward rotation (interlocked to "d003")
1: Ready, 0: Not ready
1: Tripping, 0: Normal
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
1: ON, 0: OFF
4-139
Setting

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sj700d-3 series

Table of Contents